EB-430BC6-B01 C
8.95 kW
Defrost: None
Product code: EB-330BE4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,603 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 44.3 m² |
| Inner volume | 7.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 54 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.9 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-330BE4-B01 C | None |
|---|---|
| EB-330BE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.87 | 3.95 | 4.02 | 4.09 | 4.12 | 4.12 | 4.10 | 4.17 | 4.43 | 4.81 | 4.70 | 4.66 | 4.61 | 4.53 |
| 5 | 4.80 | 4.96 | 5.11 | 5.24 | 5.31 | 5.34 | 5.32 | 5.39 | 5.72 | 6.20 | 6.03 | 5.96 | 5.86 | 5.71 |
| 6 | 5.65 | 5.90 | 6.13 | 6.34 | 6.48 | 6.56 | 6.57 | 6.65 | 7.05 | 7.65 | 7.43 | 7.34 | 7.20 | 6.98 |
| 7 | 6.40 | 6.76 | 7.08 | 7.37 | 7.56 | 7.68 | 7.72 | 7.82 | 8.30 | 9.01 | 8.78 | 8.68 | 8.53 | 8.27 |
| 8 | 7.17 | 7.62 | 8.04 | 8.41 | 8.64 | 8.79 | 8.86 | 8.98 | 9.53 | 10.34 | 10.08 | 9.96 | 9.78 | 9.47 |
| 9 | 7.81 | 8.39 | 8.92 | 9.39 | 9.71 | 9.92 | 10.02 | 10.14 | 10.77 | 11.68 | 11.40 | 11.26 | 11.04 | 10.68 |
| 10 | ≈ 8.40 | 9.11 | 9.76 | 10.34 | 10.75 | 11.02 | 11.12 | 11.29 | 11.99 | 13.01 | 12.70 | 12.55 | 12.32 | 11.91 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.698 |
| SC2 | 0 | 8 | 8.977 |
| SC3 | -18 | 7 | 7.457 |
| SC4 | -25 | 6 | 6.133 |
| SC5 | -34 | 6 | 5.707 |
| A | 1857 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.