EB-435AE6-B01 C
19.69 kW
Defrost: None
Product code: EB-340AE6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 9,536 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 62.4 m² |
| Inner volume | 15.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 100 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EB-340AE6-B01 C | None |
|---|---|
| EB-340AE6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.31 | 8.47 | 8.63 | 8.76 | 8.82 | 8.80 | 8.73 | 8.85 | 9.40 | 10.17 | 9.91 | 9.82 | 9.69 | 9.51 |
| 5 | 10.37 | 10.74 | 11.09 | 11.38 | 11.55 | 11.61 | 11.58 | 11.70 | 12.41 | 13.44 | 13.07 | 12.92 | 12.71 | 12.38 |
| 6 | 12.17 | 12.74 | 13.27 | 13.75 | 14.06 | 14.25 | 14.33 | 14.52 | 15.43 | 16.76 | 16.37 | 16.22 | 15.95 | 15.48 |
| 7 | 13.94 | 14.72 | 15.44 | 16.02 | 16.47 | 16.76 | 16.90 | 17.12 | 18.19 | 19.76 | 19.31 | 19.12 | 18.81 | 18.27 |
| 8 | 15.47 | 16.51 | 17.46 | 18.31 | 18.91 | 19.28 | 19.46 | 19.74 | 20.98 | 22.79 | 22.29 | 22.05 | 21.68 | 21.00 |
| 9 | 16.87 | 18.18 | 19.39 | 20.48 | 21.24 | 21.76 | 21.98 | 22.33 | 23.74 | 25.78 | 25.24 | 24.97 | 24.55 | 23.78 |
| 10 | ≈ 18.13 | 19.73 | 21.23 | 22.56 | 23.39 | 24.08 | 24.50 | 24.94 | 26.53 | 28.85 | 28.27 | 27.97 | 27.47 | 26.60 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 28.265 |
| SC2 | 0 | 8 | 19.743 |
| SC3 | -18 | 7 | 16.225 |
| SC4 | -25 | 6 | 13.272 |
| SC5 | -34 | 6 | 12.309 |
| A | 2317 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 1985 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2317 mm |
|---|---|
| Width | 520 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.