EB-445AC7-B07 C
21.55 kW
Defrost: None
Product code: EB-345AE7-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 13,791 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 54.4 m² |
| Inner volume | 15.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 113 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| EB-345AE7-B01 C | None |
|---|---|
| EB-345AE7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.88 | 9.09 | 9.27 | 9.41 | 9.44 | 9.37 | 9.24 | 9.43 | 10.03 | 10.84 | 10.54 | 10.44 | 10.29 | 10.01 |
| 5 | 11.14 | 11.59 | 12.01 | 12.37 | 12.59 | 12.68 | 12.60 | 12.80 | 13.58 | 14.70 | 14.25 | 14.08 | 13.84 | 13.49 |
| 6 | 13.05 | 13.75 | 14.39 | 14.95 | 15.31 | 15.51 | 15.56 | 15.82 | 16.82 | 18.27 | 17.83 | 17.65 | 17.39 | 16.97 |
| 7 | 14.95 | 15.91 | 16.78 | 17.55 | 18.07 | 18.33 | 18.46 | 18.76 | 19.94 | 21.67 | 21.13 | 20.92 | 20.58 | 20.03 |
| 8 | 16.57 | 17.84 | 19.00 | 20.03 | 20.75 | 21.19 | 21.41 | 21.68 | 23.02 | 25.03 | 24.45 | 24.20 | 23.80 | 23.13 |
| 9 | ≈ 18.04 | 19.64 | 21.12 | 22.43 | 23.20 | 23.83 | 24.18 | 24.63 | 26.19 | 28.48 | 27.86 | 27.57 | 27.10 | 26.29 |
| 10 | ≈ 19.36 | 21.29 | 23.11 | 24.50 | 25.70 | 26.52 | 27.02 | 27.58 | 29.34 | 31.92 | 31.28 | 30.96 | 30.45 | 29.50 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 31.279 |
| SC2 | 0 | 8 | 21.681 |
| SC3 | -18 | 7 | 17.783 |
| SC4 | -25 | 6 | 14.392 |
| SC5 | -34 | 6 | 13.214 |
| A | 2317 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 1985 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2317 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.