EC-A-120BC6-C25 C
0.32 kW
Defrost: None
Product code: EC-A-120EC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 241 m³/h |
|---|---|
| Air throw | 3 m |
| External surface | 1.6 m² |
| Inner volume | 0.2 dm³ |
| Fin spacing | 4.0 mm |
| Fin material | Aluminium |
| Net weight | 5 kg |
| Quantity | 1 |
|---|---|
| Diameter | 200 mm |
| Speed | 1,300 rpm |
| Power | 65 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 34.0 dB(A) |
|---|---|
| Sound power | 55.0 dB(A) |
| Energy class | E |
| Inlet | Ø1/4" |
|---|---|
| Outlet | Ø1/4" |
| EC-A-120EC4-C25 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.14 | 0.14 | 0.14 | 0.13 | 0.13 | 0.13 | 0.13 | 0.13 | 0.14 | 0.15 | 0.15 | 0.15 | 0.14 | 0.14 |
| 5 | 0.19 | 0.19 | 0.18 | 0.18 | 0.18 | 0.18 | 0.17 | 0.17 | 0.18 | 0.20 | 0.19 | 0.19 | 0.19 | 0.18 |
| 6 | 0.24 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.22 | 0.22 | 0.23 | 0.25 | 0.24 | 0.24 | 0.23 | 0.23 |
| 7 | 0.28 | 0.28 | 0.29 | 0.29 | 0.28 | 0.28 | 0.27 | 0.27 | 0.29 | 0.31 | 0.30 | 0.29 | 0.29 | 0.27 |
| 8 | 0.32 | 0.33 | 0.33 | 0.34 | 0.34 | 0.34 | 0.33 | 0.33 | 0.35 | 0.37 | 0.36 | 0.35 | 0.34 | 0.33 |
| 9 | 0.36 | 0.37 | 0.38 | 0.38 | 0.39 | 0.39 | 0.38 | 0.38 | 0.41 | 0.44 | 0.42 | 0.41 | 0.40 | 0.39 |
| 10 | 0.39 | 0.41 | 0.42 | 0.43 | 0.43 | 0.44 | 0.43 | 0.43 | 0.46 | 0.49 | 0.48 | 0.47 | 0.46 | 0.44 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 0.478 |
| SC2 | 0 | 8 | 0.330 |
| SC3 | -18 | 7 | 0.286 |
| SC4 | -25 | 6 | 0.233 |
| SC5 | -34 | 6 | 0.235 |
| A | 395 mm |
|---|---|
| B | 125 mm |
| C | 415 mm |
| E | 180 mm |
| D | 270 mm |
| D IN | 1 x Ø1/4" |
| D OUT | 1 x Ø1/4" |
| Length | 395 mm |
|---|---|
| Width | 415 mm |
| Height | 125 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.