ED-DP-145AC4-B24 C
7.32 kW
Defrost: None
Product code: ED-DP-145AE7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,445 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 30.5 m² |
| Inner volume | 10.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 74 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 66.0 dB(A) |
| Energy class | A |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-DP-145AE7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.30 | 3.25 | 3.23 | 3.22 | 3.20 | 3.17 | 3.13 | 3.18 | 3.38 | 3.66 | 3.58 | 3.55 | 3.51 | 3.46 |
| 5 | 4.24 | 4.21 | 4.21 | 4.22 | 4.21 | 4.17 | 4.12 | 4.16 | 4.41 | 4.77 | 4.63 | 4.58 | 4.52 | 4.42 |
| 6 | 5.16 | 5.19 | 5.23 | 5.27 | 5.27 | 5.24 | 5.18 | 5.21 | 5.52 | 5.96 | 5.76 | 5.69 | 5.59 | 5.43 |
| 7 | 6.06 | 6.15 | 6.24 | 6.33 | 6.36 | 6.34 | 6.29 | 6.31 | 6.67 | 7.21 | 6.96 | 6.87 | 6.73 | 6.50 |
| 8 | 6.95 | 7.11 | 7.26 | 7.39 | 7.46 | 7.46 | 7.42 | 7.44 | 7.87 | 8.49 | 8.21 | 8.10 | 7.92 | 7.63 |
| 9 | 7.77 | 8.01 | 8.25 | 8.45 | 8.56 | 8.60 | 8.56 | 8.60 | 9.09 | 9.81 | 9.50 | 9.37 | 9.16 | 8.81 |
| 10 | 8.51 | 8.84 | 9.16 | 9.43 | 9.62 | 9.71 | 9.72 | 9.77 | 10.33 | 11.15 | 10.81 | 10.65 | 10.42 | 10.02 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.805 |
| SC2 | 0 | 8 | 7.441 |
| SC3 | -18 | 7 | 6.346 |
| SC4 | -25 | 6 | 5.225 |
| SC5 | -34 | 6 | 5.173 |
| A | 1148 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 835 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1148 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.