ED-DP-435AC7-B22 C
11.68 kW
Defrost: None
Product code: ED-DP-240AE4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,069 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 73.0 m² |
| Inner volume | 15.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 107 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | A |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-DP-240AE4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.03 | 5.18 | 5.31 | 5.43 | 5.49 | 5.50 | 5.46 | 5.59 | 5.95 | 6.47 | 6.31 | 6.25 | 6.17 | 6.06 |
| 5 | 6.14 | 6.40 | 6.65 | 6.85 | 6.97 | 7.01 | 6.98 | 7.09 | 7.53 | 8.17 | 7.93 | 7.83 | 7.68 | 7.43 |
| 6 | 7.22 | 7.61 | 7.97 | 8.27 | 8.46 | 8.53 | 8.52 | 8.63 | 9.15 | 9.92 | 9.60 | 9.47 | 9.26 | 8.92 |
| 7 | 8.15 | 8.68 | 9.17 | 9.59 | 9.87 | 9.99 | 10.03 | 10.17 | 10.78 | 11.66 | 11.30 | 11.13 | 10.88 | 10.44 |
| 8 | 8.98 | 9.66 | 10.30 | 10.77 | 11.15 | 11.37 | 11.45 | 11.61 | 12.32 | 13.34 | 12.97 | 12.78 | 12.50 | 12.00 |
| 9 | ≈ 9.73 | 10.57 | 11.27 | 11.95 | 12.44 | 12.74 | 12.87 | 13.06 | 13.85 | 15.00 | 14.59 | 14.38 | 14.06 | 13.49 |
| 10 | 10.39 | 11.32 | 12.25 | 13.09 | 13.69 | 14.09 | 14.28 | 14.50 | 15.39 | 16.66 | 16.22 | 16.00 | 15.63 | 14.98 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.223 |
| SC2 | 0 | 8 | 11.612 |
| SC3 | -18 | 7 | 9.720 |
| SC4 | -25 | 6 | 7.969 |
| SC5 | -34 | 6 | 7.311 |
| A | 1548 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1548 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.