ED-DP-440AE7-B22 C
20.83 kW
Defrost: None
Product code: ED-DP-345AE7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,334 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 91.6 m² |
| Inner volume | 32.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 173 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 570 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | A |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-DP-345AE7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.49 | 9.36 | 9.30 | 9.28 | 9.21 | 9.12 | 9.01 | 9.15 | 9.73 | 10.53 | 10.28 | 10.20 | 10.09 | 9.92 |
| 5 | 12.20 | 12.15 | 12.16 | 12.20 | 12.16 | 12.06 | 11.91 | 12.03 | 12.75 | 13.78 | 13.37 | 13.24 | 13.04 | 12.76 |
| 6 | 14.86 | 14.96 | 15.09 | 15.24 | 15.26 | 15.18 | 15.01 | 15.10 | 15.98 | 17.26 | 16.70 | 16.49 | 16.19 | 15.71 |
| 7 | 17.51 | 17.78 | 18.02 | 18.31 | 18.42 | 18.39 | 18.24 | 18.31 | 19.37 | 20.93 | 20.22 | 19.94 | 19.53 | 18.86 |
| 8 | 19.97 | 20.48 | 20.97 | 21.41 | 21.63 | 21.64 | 21.53 | 21.62 | 22.87 | 24.69 | 23.90 | 23.56 | 23.05 | 22.22 |
| 9 | 22.24 | 22.99 | 23.71 | 24.37 | 24.77 | 24.93 | 24.87 | 24.98 | 26.44 | 28.55 | 27.67 | 27.27 | 26.68 | 25.69 |
| 10 | 24.30 | 25.31 | 26.25 | 27.09 | 27.64 | 27.88 | 27.98 | 28.24 | 29.94 | 32.41 | 31.46 | 31.02 | 30.35 | 29.21 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 31.456 |
| SC2 | 0 | 8 | 21.617 |
| SC3 | -18 | 7 | 18.370 |
| SC4 | -25 | 6 | 15.094 |
| SC5 | -34 | 6 | 14.899 |
| A | 2748 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 2435 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2748 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.