ED-DP-340AE7-B22 C
14.92 kW
Defrost: None
Product code: ED-DP-435AC4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,287 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 73.0 m² |
| Inner volume | 15.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 147 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 945 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 66.0 dB(A) |
| Energy class | A |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-DP-435AC4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.48 | 6.51 | 6.56 | 6.61 | 6.62 | 6.60 | 6.55 | 6.65 | 7.08 | 7.67 | 7.50 | 7.44 | 7.36 | 7.25 |
| 5 | 8.15 | 8.29 | 8.43 | 8.56 | 8.61 | 8.61 | 8.55 | 8.64 | 9.17 | 9.93 | 9.65 | 9.55 | 9.41 | 9.20 |
| 6 | 9.79 | 10.07 | 10.33 | 10.56 | 10.66 | 10.69 | 10.65 | 10.73 | 11.37 | 12.31 | 11.95 | 11.81 | 11.60 | 11.26 |
| 7 | 11.25 | 11.68 | 12.09 | 12.45 | 12.68 | 12.81 | 12.81 | 12.87 | 13.64 | 14.77 | 14.34 | 14.17 | 13.90 | 13.46 |
| 8 | 12.56 | 13.17 | 13.72 | 14.15 | 14.48 | 14.67 | 14.74 | 14.90 | 15.81 | 17.15 | 16.73 | 16.53 | 16.25 | 15.73 |
| 9 | 13.77 | 14.57 | 15.22 | 15.86 | 16.29 | 16.55 | 16.67 | 16.86 | 17.90 | 19.40 | 18.94 | 18.72 | 18.39 | 17.83 |
| 10 | 14.88 | 15.81 | 16.72 | 17.52 | 18.07 | 18.43 | 18.61 | 18.84 | 19.99 | 21.68 | 21.17 | 20.93 | 20.56 | 19.92 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.170 |
| SC2 | 0 | 8 | 14.899 |
| SC3 | -18 | 7 | 12.558 |
| SC4 | -25 | 6 | 10.327 |
| SC5 | -34 | 6 | 9.865 |
| A | 2748 mm |
|---|---|
| B | 900 mm |
| C | 325 mm |
| F | 940 mm |
| G | 410 mm |
| E1 | 2435 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2748 mm |
|---|---|
| Width | 900 mm |
| Height | 410 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.