ED-DP-445AE7-B24 C
30.63 kW
Defrost: None
Product code: ED-DP-445AC4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 14,310 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 129.9 m² |
| Inner volume | 29.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 218 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 760 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | B |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-DP-445AC4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.04 | 13.00 | 13.01 | 13.04 | 13.00 | 12.91 | 12.77 | 12.97 | 13.78 | 14.92 | 14.58 | 14.46 | 14.31 | 14.08 |
| 5 | 16.72 | 16.80 | 16.98 | 17.15 | 17.18 | 17.09 | 16.92 | 17.09 | 18.13 | 19.61 | 19.05 | 18.86 | 18.59 | 18.20 |
| 6 | 20.21 | 20.65 | 21.06 | 21.43 | 21.58 | 21.53 | 21.36 | 21.50 | 22.78 | 24.62 | 23.85 | 23.56 | 23.14 | 22.48 |
| 7 | 23.32 | 24.06 | 24.77 | 25.42 | 25.81 | 26.00 | 25.99 | 26.08 | 27.63 | 29.89 | 28.95 | 28.59 | 28.04 | 27.15 |
| 8 | 26.14 | 27.24 | 28.12 | 29.03 | 29.60 | 29.90 | 29.99 | 30.29 | 32.13 | 34.83 | 33.95 | 33.56 | 33.00 | 32.02 |
| 9 | 28.77 | 30.11 | 31.46 | 32.65 | 33.41 | 33.87 | 34.04 | 34.39 | 36.49 | 39.54 | 38.56 | 38.12 | 37.45 | 36.33 |
| 10 | 30.98 | 32.95 | 34.67 | 36.19 | 37.20 | 37.82 | 38.11 | 38.53 | 40.88 | 44.31 | 43.23 | 42.73 | 41.97 | 40.67 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 43.230 |
| SC2 | 0 | 8 | 30.286 |
| SC3 | -18 | 7 | 25.604 |
| SC4 | -25 | 6 | 21.064 |
| SC5 | -34 | 6 | 20.326 |
| A | 3548 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 570 mm |
| E1 | 3235 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3548 mm |
|---|---|
| Width | 1050 mm |
| Height | 570 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.