ED-130AE7-C21 C
2.61 kW
Defrost: None
Product code: ED-130AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 1,331 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 9.8 m² |
| Inner volume | 1.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 33 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.1 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø12,7 |
| ED-130AC4-C21 C | None |
|---|---|
| ED-130AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.99 | 1.04 | 1.08 | 1.12 | 1.14 | 1.15 | 1.15 | 1.18 | 1.25 | 1.36 | 1.33 | 1.32 | 1.31 | 1.28 |
| 5 | 1.21 | 1.29 | 1.36 | 1.43 | 1.47 | 1.50 | 1.51 | 1.54 | 1.64 | 1.79 | 1.75 | 1.73 | 1.71 | 1.67 |
| 6 | 1.39 | 1.51 | 1.61 | 1.70 | 1.77 | 1.81 | 1.83 | 1.87 | 1.99 | 2.17 | 2.12 | 2.11 | 2.08 | 2.04 |
| 7 | ≈ 1.58 | 1.72 | 1.86 | 1.98 | 2.06 | 2.12 | 2.15 | 2.20 | 2.34 | 2.55 | 2.50 | 2.47 | 2.44 | 2.39 |
| 8 | ≈ 1.73 | 1.91 | 2.08 | 2.23 | 2.35 | 2.43 | 2.47 | 2.52 | 2.69 | 2.93 | 2.87 | 2.85 | 2.81 | 2.75 |
| 9 | ≈ 1.79 | ≈ 2.08 | 2.29 | 2.48 | 2.60 | 2.71 | 2.78 | 2.85 | 3.03 | 3.31 | 3.26 | 3.23 | 3.19 | 3.12 |
| 10 | ≈ 1.04 | ≈ 2.24 | 2.48 | 2.68 | 2.86 | 2.99 | 3.08 | 3.17 | 3.38 | 3.69 | 3.64 | 3.62 | 3.57 | 3.49 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.642 |
| SC2 | 0 | 8 | 2.520 |
| SC3 | -18 | 7 | 2.014 |
| SC4 | -25 | 6 | 1.608 |
| SC5 | -34 | 6 | 1.419 |
| A | 848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø12,7 |
| Length | 848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.