ED-135AC4-C21 C
4.77 kW
Defrost: None
Product code: ED-140AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 3,483 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 15.3 m² |
| Inner volume | 5.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 53 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-140AC7-C21 C | None |
|---|---|
| ED-140AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.01 | 1.95 | 1.91 | 1.89 | 1.86 | 1.84 | 1.81 | 1.82 | 1.93 | 2.08 | 2.02 | 2.00 | 1.98 | 1.94 |
| 5 | 2.68 | 2.62 | 2.59 | 2.56 | 2.53 | 2.49 | 2.45 | 2.46 | 2.60 | 2.80 | 2.72 | 2.69 | 2.65 | 2.59 |
| 6 | 3.36 | 3.32 | 3.31 | 3.30 | 3.27 | 3.23 | 3.18 | 3.17 | 3.35 | 3.61 | 3.49 | 3.45 | 3.39 | 3.30 |
| 7 | 4.03 | 4.04 | 4.05 | 4.06 | 4.05 | 4.01 | 3.96 | 3.95 | 4.17 | 4.49 | 4.33 | 4.28 | 4.20 | 4.07 |
| 8 | 4.70 | 4.75 | 4.81 | 4.85 | 4.86 | 4.84 | 4.79 | 4.78 | 5.05 | 5.44 | 5.25 | 5.17 | 5.07 | 4.91 |
| 9 | 5.33 | 5.44 | 5.55 | 5.64 | 5.69 | 5.69 | 5.65 | 5.64 | 5.96 | 6.43 | 6.21 | 6.13 | 6.00 | 5.80 |
| 10 | 5.87 | 6.04 | 6.21 | 6.36 | 6.46 | 6.51 | 6.52 | 6.53 | 6.90 | 7.45 | 7.21 | 7.11 | 6.97 | 6.74 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.210 |
| SC2 | 0 | 8 | 4.777 |
| SC3 | -18 | 7 | 4.061 |
| SC4 | -25 | 6 | 3.305 |
| SC5 | -34 | 6 | 3.354 |
| A | 948 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 467 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1210 mm |
| Height | 467 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.