ED-630AE4-C25 C
18.06 kW
Defrost: None
Product code: ED-245AE7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 9,087 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 61.0 m² |
| Inner volume | 21.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 114 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 700 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| ED-245AE7-C23 C | None |
|---|---|
| ED-245AE7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.71 | 7.59 | 7.52 | 7.49 | 7.42 | 7.34 | 7.24 | 7.29 | 7.73 | 8.35 | 8.13 | 8.06 | 7.95 | 7.77 |
| 5 | 9.98 | 9.94 | 9.95 | 9.97 | 9.92 | 9.83 | 9.71 | 9.74 | 10.31 | 11.13 | 10.79 | 10.67 | 10.51 | 10.27 |
| 6 | 12.20 | 12.30 | 12.42 | 12.54 | 12.55 | 12.49 | 12.36 | 12.38 | 13.10 | 14.13 | 13.67 | 13.50 | 13.26 | 12.88 |
| 7 | 14.40 | 14.66 | 14.92 | 15.16 | 15.24 | 15.24 | 15.14 | 15.16 | 16.04 | 17.31 | 16.74 | 16.52 | 16.20 | 15.68 |
| 8 | 16.40 | 16.86 | 17.32 | 17.74 | 17.97 | 18.03 | 17.97 | 18.02 | 19.07 | 20.60 | 19.96 | 19.70 | 19.31 | 18.65 |
| 9 | 18.16 | 18.83 | 19.46 | 20.04 | 20.41 | 20.58 | 20.66 | 20.83 | 22.10 | 23.92 | 23.22 | 22.93 | 22.48 | 21.69 |
| 10 | 19.81 | 20.72 | 21.56 | 22.21 | 22.71 | 23.03 | 23.17 | 23.38 | 24.81 | 26.89 | 26.26 | 25.97 | 25.53 | 24.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 26.255 |
| SC2 | 0 | 8 | 18.017 |
| SC3 | -18 | 7 | 15.195 |
| SC4 | -25 | 6 | 12.420 |
| SC5 | -34 | 6 | 12.236 |
| A | 1948 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 441 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1948 mm |
|---|---|
| Width | 1210 mm |
| Height | 441 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.