ED-445AC4-C23 C
35.07 kW
Defrost: None
Product code: ED-250AG4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 12,282 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 182.6 m² |
| Inner volume | 40.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 184 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 1,360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.7 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| ED-250AG4-C21 C | None |
|---|---|
| ED-250AG4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.08 | 15.28 | 15.49 | 15.68 | 15.74 | 15.69 | 15.55 | 15.83 | 16.83 | 18.25 | 17.80 | 17.65 | 17.45 | 17.17 |
| 5 | 18.82 | 19.20 | 19.67 | 20.07 | 20.26 | 20.27 | 20.12 | 20.35 | 21.58 | 23.38 | 22.68 | 22.42 | 22.04 | 21.44 |
| 6 | 22.23 | 23.08 | 23.85 | 24.50 | 24.86 | 24.94 | 24.84 | 25.04 | 26.53 | 28.72 | 27.82 | 27.46 | 26.91 | 26.02 |
| 7 | 25.32 | 26.54 | 27.66 | 28.64 | 29.25 | 29.57 | 29.54 | 29.79 | 31.54 | 34.13 | 33.08 | 32.63 | 31.95 | 30.79 |
| 8 | 28.08 | 29.74 | 31.24 | 32.38 | 33.24 | 33.71 | 33.87 | 34.22 | 36.29 | 39.31 | 38.25 | 37.76 | 37.02 | 35.68 |
| 9 | 30.61 | 32.74 | 34.45 | 36.12 | 37.27 | 37.92 | 38.20 | 38.61 | 40.95 | 44.34 | 43.18 | 42.63 | 41.77 | 40.28 |
| 10 | ≈ 32.91 | 35.30 | 37.66 | 39.74 | 41.21 | 42.09 | 42.51 | 43.01 | 45.63 | 49.41 | 48.15 | 47.53 | 46.57 | 44.87 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 48.150 |
| SC2 | 0 | 8 | 34.220 |
| SC3 | -18 | 7 | 28.922 |
| SC4 | -25 | 6 | 23.849 |
| SC5 | -34 | 6 | 22.440 |
| A | 2368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 2035 mm |
| E2 | 1018 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2368 mm |
|---|---|
| Width | 1350 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.