ED-P-A-225AC4-B24 C
1.68 kW
Defrost: None
Product code: ED-P-A-225BC4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 947 m³/h |
|---|---|
| Air throw | 3 m |
| External surface | 7.4 m² |
| Inner volume | 1.9 dm³ |
| Fin spacing | 3.9 mm |
| Fin material | Aluminium |
| Net weight | 12 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 57.7 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø1/2" |
| ED-P-A-225BC4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.73 | 0.75 | 0.76 | 0.77 | 0.78 | 0.78 | 0.77 | 0.79 | 0.84 | 0.91 | 0.89 | 0.88 | 0.87 | 0.86 |
| 5 | 0.91 | 0.95 | 0.98 | 1.00 | 1.02 | 1.02 | 1.01 | 1.03 | 1.09 | 1.19 | 1.15 | 1.14 | 1.12 | 1.09 |
| 6 | 1.08 | 1.14 | 1.19 | 1.23 | 1.26 | 1.27 | 1.27 | 1.28 | 1.36 | 1.48 | 1.43 | 1.42 | 1.39 | 1.35 |
| 7 | 1.24 | 1.31 | 1.38 | 1.44 | 1.48 | 1.51 | 1.52 | 1.54 | 1.64 | 1.78 | 1.73 | 1.71 | 1.67 | 1.61 |
| 8 | 1.37 | 1.47 | 1.56 | 1.64 | 1.70 | 1.73 | 1.75 | 1.78 | 1.89 | 2.05 | 2.00 | 1.98 | 1.94 | 1.88 |
| 9 | 1.52 | 1.63 | 1.74 | 1.84 | 1.90 | 1.95 | 1.98 | 2.01 | 2.14 | 2.32 | 2.27 | 2.24 | 2.20 | 2.13 |
| 10 | 1.63 | 1.77 | 1.91 | 2.03 | 2.12 | 2.18 | 2.21 | 2.25 | 2.39 | 2.59 | 2.54 | 2.51 | 2.46 | 2.38 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.536 |
| SC2 | 0 | 8 | 1.775 |
| SC3 | -18 | 7 | 1.460 |
| SC4 | -25 | 6 | 1.186 |
| SC5 | -34 | 6 | 1.095 |
| A | 565 mm |
|---|---|
| B | 795 mm |
| C | 160 mm |
| E | 620 mm |
| D | 544 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø1/2" |
| Length | 565 mm |
|---|---|
| Width | 795 mm |
| Height | 150 mm |
Our engineers answer with a selection for your conditions.