ED-P-B-130CC6-C25 C
1.26 kW
Defrost: None
Product code: ED-P-B-130AC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 847 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 4.9 m² |
| Inner volume | 0.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 12 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 62.0 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø1/2" |
| ED-P-B-130AC4-C25 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.51 | 0.54 | 0.57 | 0.59 | 0.60 | 0.60 | 0.60 | 0.61 | 0.65 | 0.71 | 0.69 | 0.68 | 0.67 | 0.66 |
| 5 | 0.62 | 0.66 | 0.70 | 0.74 | 0.76 | 0.77 | 0.77 | 0.79 | 0.84 | 0.91 | 0.89 | 0.88 | 0.87 | 0.85 |
| 6 | 0.71 | 0.77 | 0.83 | 0.88 | 0.91 | 0.93 | 0.94 | 0.96 | 1.02 | 1.11 | 1.08 | 1.07 | 1.05 | 1.02 |
| 7 | ≈ 0.79 | 0.87 | 0.95 | 1.01 | 1.06 | 1.09 | 1.10 | 1.13 | 1.20 | 1.30 | 1.27 | 1.25 | 1.23 | 1.19 |
| 8 | ≈ 0.80 | ≈ 0.97 | 1.06 | 1.15 | 1.21 | 1.25 | 1.27 | 1.29 | 1.38 | 1.50 | 1.46 | 1.44 | 1.42 | 1.37 |
| 9 | ≈ 0.60 | ≈ 1.05 | 1.17 | 1.27 | 1.35 | 1.40 | 1.43 | 1.46 | 1.56 | 1.69 | 1.66 | 1.64 | 1.61 | 1.55 |
| 10 | ≈ 0.32 | ≈ 1.13 | 1.28 | 1.40 | 1.49 | 1.56 | 1.59 | 1.63 | 1.74 | 1.89 | 1.85 | 1.83 | 1.80 | 1.74 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 1.853 |
| SC2 | 0 | 8 | 1.294 |
| SC3 | -18 | 7 | 1.035 |
| SC4 | -25 | 6 | 0.829 |
| SC5 | -34 | 6 | 0.724 |
| A | 845 mm |
|---|---|
| B | 470 mm |
| C | 185 mm |
| E | 342 mm |
| D | 795 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø1/2" |
| Length | 845 mm |
|---|---|
| Width | 470 mm |
| Height | 185 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.