EG-A-325AD6-C25 C
2.23 kW
Defrost: None
Product code: EG-A-325BC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,313 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 9.0 m² |
| Inner volume | 1.4 dm³ |
| Fin spacing | 3.8 mm |
| Fin material | Aluminium |
| Net weight | 14 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 285 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.5 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø1/2" |
| EG-A-325BC4-C25 C | None |
|---|---|
| EG-A-325BC4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.98 | 1.00 | 1.02 | 1.03 | 1.04 | 1.03 | 1.02 | 1.05 | 1.11 | 1.21 | 1.18 | 1.17 | 1.16 | 1.14 |
| 5 | 1.23 | 1.27 | 1.31 | 1.35 | 1.37 | 1.38 | 1.37 | 1.39 | 1.48 | 1.60 | 1.56 | 1.54 | 1.52 | 1.49 |
| 6 | 1.44 | 1.51 | 1.57 | 1.63 | 1.67 | 1.69 | 1.69 | 1.72 | 1.83 | 1.99 | 1.94 | 1.92 | 1.89 | 1.85 |
| 7 | 1.65 | 1.75 | 1.84 | 1.91 | 1.96 | 1.99 | 2.00 | 2.03 | 2.16 | 2.34 | 2.29 | 2.26 | 2.23 | 2.17 |
| 8 | 1.83 | 1.96 | 2.08 | 2.18 | 2.26 | 2.30 | 2.32 | 2.35 | 2.49 | 2.70 | 2.64 | 2.61 | 2.57 | 2.50 |
| 9 | 1.99 | 2.16 | 2.31 | 2.45 | 2.52 | 2.59 | 2.62 | 2.66 | 2.83 | 3.07 | 3.00 | 2.97 | 2.92 | 2.83 |
| 10 | ≈ 2.14 | 2.34 | 2.53 | 2.68 | 2.80 | 2.88 | 2.92 | 2.98 | 3.17 | 3.44 | 3.37 | 3.33 | 3.27 | 3.17 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.366 |
| SC2 | 0 | 8 | 2.347 |
| SC3 | -18 | 7 | 1.936 |
| SC4 | -25 | 6 | 1.573 |
| SC5 | -34 | 6 | 1.454 |
| A | 1205 mm |
|---|---|
| B | 215 mm |
| C | 465 mm |
| F | 187 mm |
| E | 365 mm |
| D | 441 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø1/2" |
| Length | 1205 mm |
|---|---|
| Width | 465 mm |
| Height | 215 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.