EG-135BC7-C21 C
2.75 kW
Defrost: None
Product code: EG-225BE7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 1,212 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 11.1 m² |
| Inner volume | 2.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 27 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 61.4 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EG-225BE7-C23 C | None |
|---|---|
| EG-225BE7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.21 | 1.21 | 1.21 | 1.21 | 1.21 | 1.20 | 1.18 | 1.21 | 1.29 | 1.40 | 1.37 | 1.35 | 1.34 | 1.32 |
| 5 | 1.54 | 1.55 | 1.56 | 1.58 | 1.58 | 1.57 | 1.55 | 1.57 | 1.67 | 1.80 | 1.75 | 1.72 | 1.70 | 1.65 |
| 6 | 1.85 | 1.88 | 1.92 | 1.95 | 1.96 | 1.95 | 1.93 | 1.95 | 2.06 | 2.23 | 2.16 | 2.13 | 2.08 | 2.02 |
| 7 | 2.15 | 2.21 | 2.27 | 2.32 | 2.34 | 2.34 | 2.33 | 2.34 | 2.48 | 2.68 | 2.59 | 2.56 | 2.50 | 2.42 |
| 8 | 2.43 | 2.52 | 2.61 | 2.68 | 2.72 | 2.74 | 2.72 | 2.74 | 2.90 | 3.14 | 3.04 | 3.00 | 2.94 | 2.83 |
| 9 | 2.69 | 2.81 | 2.92 | 3.02 | 3.08 | 3.11 | 3.11 | 3.14 | 3.33 | 3.60 | 3.49 | 3.45 | 3.38 | 3.25 |
| 10 | 2.95 | 3.10 | 3.22 | 3.34 | 3.42 | 3.47 | 3.47 | 3.51 | 3.72 | 4.03 | 3.93 | 3.88 | 3.81 | 3.68 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.925 |
| SC2 | 0 | 8 | 2.743 |
| SC3 | -18 | 7 | 2.331 |
| SC4 | -25 | 6 | 1.916 |
| SC5 | -34 | 6 | 1.859 |
| A | 1066 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 378 mm |
| E | 755 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1066 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.