EG-330AB7-C25 C
4.08 kW
Defrost: None
Product code: EG-230AC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 2,094 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 15.7 m² |
| Inner volume | 2.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EG-230AC4-C25 C | None |
|---|---|
| EG-230AC4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.75 | 1.77 | 1.78 | 1.80 | 1.80 | 1.79 | 1.77 | 1.81 | 1.93 | 2.09 | 2.05 | 2.03 | 2.01 | 1.99 |
| 5 | 2.22 | 2.27 | 2.32 | 2.36 | 2.37 | 2.37 | 2.34 | 2.38 | 2.53 | 2.74 | 2.66 | 2.63 | 2.59 | 2.54 |
| 6 | 2.64 | 2.73 | 2.81 | 2.89 | 2.93 | 2.95 | 2.95 | 2.99 | 3.17 | 3.44 | 3.33 | 3.29 | 3.23 | 3.13 |
| 7 | 3.04 | 3.16 | 3.27 | 3.38 | 3.45 | 3.48 | 3.49 | 3.53 | 3.75 | 4.07 | 3.96 | 3.92 | 3.85 | 3.74 |
| 8 | 3.39 | 3.57 | 3.73 | 3.88 | 3.97 | 4.01 | 4.03 | 4.08 | 4.33 | 4.70 | 4.57 | 4.52 | 4.44 | 4.30 |
| 9 | 3.73 | 3.96 | 4.17 | 4.36 | 4.48 | 4.55 | 4.57 | 4.63 | 4.91 | 5.33 | 5.18 | 5.12 | 5.02 | 4.86 |
| 10 | 4.03 | 4.32 | 4.59 | 4.82 | 4.98 | 5.06 | 5.10 | 5.18 | 5.49 | 5.96 | 5.80 | 5.73 | 5.63 | 5.44 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.804 |
| SC2 | 0 | 8 | 4.078 |
| SC3 | -18 | 7 | 3.411 |
| SC4 | -25 | 6 | 2.809 |
| SC5 | -34 | 6 | 2.658 |
| A | 1946 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1946 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.