EG-135BE7-C21 C
3.77 kW
Defrost: None
Product code: EG-230AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,584 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 9.9 m² |
| Inner volume | 2.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 35 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.1 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EG-230AC7-C21 C | None |
|---|---|
| EG-230AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.55 | 1.55 | 1.55 | 1.55 | 1.54 | 1.52 | 1.50 | 1.52 | 1.61 | 1.74 | 1.69 | 1.67 | 1.65 | 1.61 |
| 5 | 2.00 | 2.02 | 2.05 | 2.07 | 2.07 | 2.06 | 2.04 | 2.06 | 2.18 | 2.35 | 2.28 | 2.26 | 2.22 | 2.17 |
| 6 | 2.43 | 2.49 | 2.55 | 2.60 | 2.63 | 2.63 | 2.62 | 2.63 | 2.79 | 3.02 | 2.92 | 2.89 | 2.84 | 2.75 |
| 7 | 2.79 | 2.89 | 2.98 | 3.07 | 3.13 | 3.16 | 3.17 | 3.20 | 3.40 | 3.69 | 3.61 | 3.56 | 3.50 | 3.39 |
| 8 | 3.16 | 3.29 | 3.42 | 3.53 | 3.61 | 3.65 | 3.68 | 3.72 | 3.95 | 4.29 | 4.19 | 4.15 | 4.08 | 3.98 |
| 9 | 3.49 | 3.67 | 3.84 | 3.99 | 4.09 | 4.16 | 4.19 | 4.24 | 4.50 | 4.89 | 4.78 | 4.73 | 4.66 | 4.54 |
| 10 | 3.79 | 4.02 | 4.24 | 4.43 | 4.56 | 4.65 | 4.70 | 4.77 | 5.06 | 5.49 | 5.37 | 5.32 | 5.24 | 5.10 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.371 |
| SC2 | 0 | 8 | 3.718 |
| SC3 | -18 | 7 | 3.095 |
| SC4 | -25 | 6 | 2.548 |
| SC5 | -34 | 6 | 2.441 |
| A | 1946 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1946 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.