EG-430AC4-C25 C
8.04 kW
Defrost: None
Product code: EG-235CE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 3,651 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 31.0 m² |
| Inner volume | 5.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EG-235CE4-C21 C | None |
|---|---|
| EG-235CE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.53 | 3.52 | 3.52 | 3.53 | 3.51 | 3.47 | 3.42 | 3.52 | 3.75 | 4.07 | 3.98 | 3.96 | 3.92 | 3.88 |
| 5 | 4.52 | 4.56 | 4.60 | 4.65 | 4.64 | 4.60 | 4.53 | 4.61 | 4.90 | 5.30 | 5.14 | 5.08 | 5.01 | 4.90 |
| 6 | 5.46 | 5.58 | 5.70 | 5.79 | 5.82 | 5.80 | 5.72 | 5.78 | 6.12 | 6.62 | 6.38 | 6.30 | 6.17 | 5.96 |
| 7 | 6.28 | 6.47 | 6.66 | 6.82 | 6.91 | 6.94 | 6.91 | 6.98 | 7.41 | 8.02 | 7.72 | 7.60 | 7.42 | 7.13 |
| 8 | 7.11 | 7.38 | 7.63 | 7.83 | 7.96 | 8.00 | 7.98 | 8.06 | 8.54 | 9.24 | 8.95 | 8.83 | 8.64 | 8.32 |
| 9 | 7.84 | 8.21 | 8.55 | 8.84 | 9.01 | 9.07 | 9.07 | 9.15 | 9.70 | 10.48 | 10.15 | 10.00 | 9.77 | 9.39 |
| 10 | 8.53 | 9.01 | 9.45 | 9.82 | 10.05 | 10.16 | 10.17 | 10.26 | 10.87 | 11.74 | 11.37 | 11.20 | 10.94 | 10.48 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.374 |
| SC2 | 0 | 8 | 8.060 |
| SC3 | -18 | 7 | 6.864 |
| SC4 | -25 | 6 | 5.697 |
| SC5 | -34 | 6 | 5.493 |
| A | 1747 mm |
|---|---|
| B | 685 mm |
| C | 355 mm |
| F | 630 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1747 mm |
|---|---|
| Width | 685 mm |
| Height | 355 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.