EG-230BE7-C25 C
4.21 kW
Defrost: None
Product code: EG-325BE7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,818 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 16.7 m² |
| Inner volume | 4.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.4 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EG-325BE7-C23 C | None |
|---|---|
| EG-325BE7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.81 | 1.84 | 1.87 | 1.89 | 1.90 | 1.89 | 1.87 | 1.92 | 2.05 | 2.22 | 2.17 | 2.15 | 2.12 | 2.09 |
| 5 | 2.26 | 2.32 | 2.38 | 2.43 | 2.46 | 2.46 | 2.44 | 2.48 | 2.63 | 2.85 | 2.76 | 2.73 | 2.68 | 2.60 |
| 6 | 2.68 | 2.79 | 2.89 | 2.97 | 3.02 | 3.03 | 3.02 | 3.06 | 3.24 | 3.51 | 3.40 | 3.36 | 3.30 | 3.19 |
| 7 | 3.07 | 3.22 | 3.36 | 3.49 | 3.57 | 3.60 | 3.60 | 3.65 | 3.87 | 4.19 | 4.06 | 4.01 | 3.94 | 3.81 |
| 8 | 3.42 | 3.62 | 3.81 | 3.97 | 4.07 | 4.13 | 4.15 | 4.20 | 4.46 | 4.84 | 4.72 | 4.67 | 4.59 | 4.44 |
| 9 | 3.78 | 4.03 | 4.25 | 4.43 | 4.57 | 4.65 | 4.68 | 4.75 | 5.04 | 5.46 | 5.34 | 5.28 | 5.19 | 5.02 |
| 10 | 4.08 | 4.38 | 4.67 | 4.91 | 5.08 | 5.19 | 5.22 | 5.30 | 5.63 | 6.10 | 5.96 | 5.90 | 5.79 | 5.61 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.961 |
| SC2 | 0 | 8 | 4.204 |
| SC3 | -18 | 7 | 3.522 |
| SC4 | -25 | 6 | 2.885 |
| SC5 | -34 | 6 | 2.708 |
| A | 1426 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 378 mm |
| E2 | 360 mm |
| E | 1115 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1426 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.