EG-235BC7-C21 C
5.58 kW
Defrost: None
Product code: EG-330AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 3,876 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 14.9 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 49 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.1 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-330AC7-C21 C | None |
|---|---|
| EG-330AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.36 | 2.35 | 2.35 | 2.35 | 2.33 | 2.31 | 2.27 | 2.30 | 2.44 | 2.64 | 2.56 | 2.54 | 2.50 | 2.44 |
| 5 | 3.04 | 3.07 | 3.11 | 3.14 | 3.15 | 3.13 | 3.10 | 3.12 | 3.31 | 3.57 | 3.46 | 3.42 | 3.37 | 3.29 |
| 6 | 3.69 | 3.77 | 3.86 | 3.95 | 3.99 | 3.99 | 3.97 | 3.99 | 4.23 | 4.57 | 4.43 | 4.38 | 4.30 | 4.18 |
| 7 | 4.24 | 4.39 | 4.52 | 4.65 | 4.73 | 4.78 | 4.80 | 4.85 | 5.15 | 5.59 | 5.45 | 5.40 | 5.30 | 5.14 |
| 8 | 4.81 | 5.00 | 5.19 | 5.35 | 5.46 | 5.53 | 5.57 | 5.63 | 5.97 | 6.48 | 6.33 | 6.27 | 6.18 | 6.02 |
| 9 | 5.31 | 5.57 | 5.82 | 6.05 | 6.20 | 6.29 | 6.34 | 6.41 | 6.81 | 7.39 | 7.23 | 7.16 | 7.05 | 6.86 |
| 10 | 5.77 | 6.12 | 6.44 | 6.71 | 6.91 | 7.04 | 7.12 | 7.21 | 7.64 | 8.30 | 8.12 | 8.04 | 7.92 | 7.71 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.124 |
| SC2 | 0 | 8 | 5.625 |
| SC3 | -18 | 7 | 4.688 |
| SC4 | -25 | 6 | 3.862 |
| SC5 | -34 | 6 | 3.708 |
| A | 2746 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 2746 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.