EG-230AE7-C21 C
4.60 kW
Defrost: None
Product code: EG-425AB4-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 2,891 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 17.6 m² |
| Inner volume | 2.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 45 kg |
| Quantity | 4 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 64.4 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EG-425AB4-C23 C | None |
|---|---|
| EG-425AB4-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.96 | 1.98 | 2.01 | 2.03 | 2.03 | 2.02 | 1.99 | 2.03 | 2.16 | 2.34 | 2.29 | 2.27 | 2.24 | 2.20 |
| 5 | 2.48 | 2.55 | 2.61 | 2.68 | 2.71 | 2.71 | 2.69 | 2.73 | 2.89 | 3.13 | 3.04 | 3.01 | 2.96 | 2.89 |
| 6 | 2.92 | 3.04 | 3.14 | 3.24 | 3.30 | 3.33 | 3.33 | 3.39 | 3.60 | 3.91 | 3.82 | 3.78 | 3.73 | 3.64 |
| 7 | 3.36 | 3.53 | 3.68 | 3.81 | 3.89 | 3.94 | 3.95 | 4.01 | 4.26 | 4.62 | 4.51 | 4.46 | 4.39 | 4.27 |
| 8 | 3.75 | 3.98 | 4.18 | 4.36 | 4.48 | 4.55 | 4.58 | 4.64 | 4.93 | 5.34 | 5.21 | 5.15 | 5.06 | 4.92 |
| 9 | 4.11 | 4.40 | 4.67 | 4.90 | 5.04 | 5.14 | 5.19 | 5.27 | 5.60 | 6.08 | 5.93 | 5.86 | 5.76 | 5.58 |
| 10 | 4.43 | 4.80 | 5.13 | 5.39 | 5.60 | 5.74 | 5.81 | 5.91 | 6.28 | 6.82 | 6.66 | 6.58 | 6.46 | 6.26 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.656 |
| SC2 | 0 | 8 | 4.641 |
| SC3 | -18 | 7 | 3.848 |
| SC4 | -25 | 6 | 3.143 |
| SC5 | -34 | 6 | 2.949 |
| A | 2746 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 618 mm |
| E2 | 600 mm |
| E | 2435 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 2746 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.