EG-330AC4-C21 C
6.62 kW
Defrost: None
Product code: EG-430AC7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 4,562 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 19.8 m² |
| Inner volume | 5.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 61 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EG-430AC7-C25 C | None |
|---|---|
| EG-430AC7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.73 | 2.79 | 2.84 | 2.88 | 2.90 | 2.89 | 2.86 | 2.92 | 3.10 | 3.36 | 3.28 | 3.25 | 3.21 | 3.15 |
| 5 | 3.44 | 3.57 | 3.68 | 3.78 | 3.84 | 3.86 | 3.85 | 3.90 | 4.14 | 4.49 | 4.36 | 4.32 | 4.25 | 4.15 |
| 6 | 4.05 | 4.24 | 4.43 | 4.59 | 4.70 | 4.76 | 4.79 | 4.87 | 5.18 | 5.63 | 5.51 | 5.46 | 5.38 | 5.24 |
| 7 | 4.64 | 4.91 | 5.16 | 5.36 | 5.52 | 5.62 | 5.67 | 5.76 | 6.12 | 6.66 | 6.51 | 6.45 | 6.35 | 6.19 |
| 8 | 5.16 | 5.52 | 5.85 | 6.14 | 6.35 | 6.48 | 6.55 | 6.66 | 7.08 | 7.70 | 7.54 | 7.45 | 7.33 | 7.13 |
| 9 | 5.63 | 6.08 | 6.50 | 6.88 | 7.14 | 7.33 | 7.41 | 7.54 | 8.02 | 8.73 | 8.55 | 8.46 | 8.33 | 8.09 |
| 10 | ≈ 6.06 | 6.61 | 7.12 | 7.58 | 7.87 | 8.11 | 8.26 | 8.43 | 8.98 | 9.77 | 9.59 | 9.49 | 9.34 | 9.07 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.587 |
| SC2 | 0 | 8 | 6.656 |
| SC3 | -18 | 7 | 5.432 |
| SC4 | -25 | 6 | 4.425 |
| SC5 | -34 | 6 | 4.094 |
| A | 3546 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 3546 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.