EM-230AB4-C21 C
7.50 kW
Defrost: None
Product code: EM-230AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,377 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 59.0 m² |
| Inner volume | 10.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 86 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.6 dB(A) |
| Energy class | A |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EM-230AC4-C21 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.68 | 3.86 | 4.02 | 4.16 | 4.27 | 4.34 | 4.38 | 4.43 | 4.71 | 5.12 | 5.02 | 4.98 | 4.93 | 4.83 |
| 5 | 4.43 | 4.70 | 4.96 | 5.19 | 5.35 | 5.47 | 5.55 | 5.62 | 5.98 | 6.50 | 6.39 | 6.34 | 6.27 | 6.15 |
| 6 | 5.10 | 5.47 | 5.82 | 6.13 | 6.37 | 6.54 | 6.67 | 6.77 | 7.21 | 7.85 | 7.73 | 7.68 | 7.60 | 7.47 |
| 7 | ≈ 5.70 | 6.18 | 6.64 | 7.05 | 7.36 | 7.59 | 7.76 | 7.89 | 8.41 | 9.16 | 9.04 | 8.98 | 8.89 | 8.72 |
| 8 | ≈ 6.32 | 6.90 | 7.46 | 7.96 | 8.35 | 8.64 | 8.84 | 9.01 | 9.60 | 10.48 | 10.31 | 10.25 | 10.15 | 9.97 |
| 9 | ≈ 6.81 | 7.51 | 8.19 | 8.81 | 9.29 | 9.66 | 9.87 | 10.09 | 10.76 | 11.75 | 11.61 | 11.54 | 11.44 | 11.24 |
| 10 | ≈ 6.06 | ≈ 8.07 | 8.87 | 9.61 | 10.09 | 10.57 | 10.91 | 11.18 | 11.93 | 13.04 | 12.91 | 12.84 | 12.73 | 12.51 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.911 |
| SC2 | 0 | 8 | 9.009 |
| SC3 | -18 | 7 | 7.181 |
| SC4 | -25 | 6 | 5.820 |
| SC5 | -34 | 6 | 5.187 |
| A | 3900 mm |
|---|---|
| B | 600 mm |
| C | 366 mm |
| F | 650 mm |
| G | 700 mm |
| E | 1515 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 3900 mm |
|---|---|
| Width | 600 mm |
| Height | 366 mm |
Our engineers answer with a selection for your conditions.