EM-235AB4-C21 C
13.55 kW
Defrost: None
Product code: EM-235AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,354 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 106.2 m² |
| Inner volume | 18.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 120 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.4 dB(A) |
| Energy class | A |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EM-235AC4-C21 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.52 | 7.69 | 7.87 | 8.05 | 8.17 | 8.25 | 8.29 | 8.35 | 8.86 | 9.62 | 9.43 | 9.35 | 9.24 | 9.06 |
| 5 | 9.19 | 9.51 | 9.82 | 10.11 | 10.32 | 10.46 | 10.55 | 10.63 | 11.29 | 12.25 | 12.02 | 11.92 | 11.78 | 11.54 |
| 6 | 10.75 | 11.23 | 11.70 | 12.13 | 12.45 | 12.67 | 12.82 | 12.94 | 13.75 | 14.94 | 14.67 | 14.56 | 14.38 | 14.10 |
| 7 | 12.14 | 12.81 | 13.44 | 14.02 | 14.45 | 14.76 | 14.98 | 15.17 | 16.13 | 17.55 | 17.27 | 17.15 | 16.97 | 16.66 |
| 8 | 13.56 | 14.41 | 15.20 | 15.86 | 16.42 | 16.82 | 17.11 | 17.35 | 18.46 | 20.09 | 19.79 | 19.66 | 19.45 | 19.09 |
| 9 | 14.75 | 15.82 | 16.82 | 17.72 | 18.40 | 18.90 | 19.24 | 19.53 | 20.79 | 22.64 | 22.32 | 22.17 | 21.94 | 21.52 |
| 10 | ≈ 15.84 | 17.14 | 18.36 | 19.47 | 20.30 | 20.92 | 21.38 | 21.66 | 23.08 | 25.13 | 24.80 | 24.64 | 24.40 | 23.98 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.796 |
| SC2 | 0 | 8 | 17.347 |
| SC3 | -18 | 7 | 14.207 |
| SC4 | -25 | 6 | 11.698 |
| SC5 | -34 | 6 | 10.863 |
| A | 4500 mm |
|---|---|
| B | 600 mm |
| C | 462 mm |
| F | 650 mm |
| G | 700 mm |
| E | 1815 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 4500 mm |
|---|---|
| Width | 600 mm |
| Height | 462 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.