EK-DI-163AC10-A08 C
15.70 kW
Defrost: None
Product code: EK-DI-163AC10-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 19,071 m³/h |
|---|---|
| External surface | 52.9 m² |
| Inner volume | 22.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 199 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EK-DI-163AC10-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.10 | 6.85 | 6.69 | 6.58 | 6.48 | 6.37 | 6.27 | 6.22 | 6.57 | 7.07 | 6.86 | 6.78 | 6.67 | 6.51 |
| 5 | 8.47 | 8.27 | 8.12 | 8.92 | 8.79 | 8.64 | 8.50 | 8.42 | 8.88 | 9.55 | 9.23 | 9.12 | 8.96 | 8.71 |
| 6 | 10.63 | 10.47 | 10.37 | 11.44 | 11.32 | 11.16 | 10.99 | 10.87 | 11.47 | 12.32 | 11.90 | 11.74 | 11.52 | 11.19 |
| 7 | 12.73 | 12.68 | 12.67 | 14.09 | 14.00 | 13.85 | 13.67 | 13.55 | 14.28 | 15.35 | 14.82 | 14.62 | 14.33 | 13.89 |
| 8 | 14.75 | 14.86 | 14.97 | 16.76 | 16.75 | 16.66 | 16.48 | 16.36 | 17.26 | 18.57 | 17.94 | 17.70 | 17.35 | 16.80 |
| 9 | 18.52 | 18.80 | 19.10 | 19.38 | 19.49 | 19.47 | 19.37 | 19.27 | 20.36 | 21.93 | 21.22 | 20.95 | 20.54 | 19.88 |
| 10 | 20.31 | 20.83 | 21.33 | 21.80 | 22.10 | 22.27 | 22.29 | 22.24 | 23.52 | 25.37 | 24.61 | 24.30 | 23.85 | 23.11 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.28 | 6.07 | 5.93 | 5.86 | 5.77 | 5.70 | 5.63 | 5.62 | 5.93 | 6.40 | 6.23 | 6.16 | 6.07 | 5.94 |
| 5 | 7.46 | 7.26 | 7.13 | 7.84 | 7.73 | 7.62 | 7.51 | 7.48 | 7.90 | 8.51 | 8.26 | 8.17 | 8.04 | 7.85 |
| 6 | 9.33 | 9.14 | 9.03 | 9.97 | 9.87 | 9.74 | 9.60 | 9.54 | 10.07 | 10.84 | 10.49 | 10.37 | 10.19 | 9.92 |
| 7 | 11.18 | 11.07 | 11.01 | 12.20 | 12.12 | 12.00 | 11.85 | 11.76 | 12.42 | 13.36 | 12.92 | 12.75 | 12.52 | 12.15 |
| 8 | 12.99 | 12.98 | 13.00 | 14.50 | 14.46 | 14.36 | 14.21 | 14.11 | 14.90 | 16.04 | 15.51 | 15.31 | 15.02 | 14.56 |
| 9 | 16.37 | 16.50 | 16.65 | 16.81 | 16.84 | 16.77 | 16.63 | 16.55 | 17.47 | 18.83 | 18.22 | 17.99 | 17.65 | 17.10 |
| 10 | 18.21 | 18.48 | 18.78 | 19.06 | 19.18 | 19.19 | 19.11 | 19.04 | 20.13 | 21.71 | 21.04 | 20.77 | 20.39 | 19.76 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 24.605 | 21.041 |
| SC2 | 0 | 8 | 16.357 | 14.113 |
| SC3 | -18 | 7 | 14.060 | 12.175 |
| SC4 | -25 | 6 | 10.374 | 9.033 |
| SC5 | -34 | 6 | 10.609 | 9.301 |
| A | 1725 mm |
|---|---|
| B | 900 mm |
| C | 1150 mm |
| F | 860 mm |
| G | 1440 mm |
| E | 1335 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1725 mm |
|---|---|
| Width | 1440 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.