EK-DI-163AE10-A08 C
22.03 kW
Defrost: None
Product code: EK-DI-163AE10-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 18,377 m³/h |
|---|---|
| External surface | 79.4 m² |
| Inner volume | 33.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 227 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EK-DI-163AE10-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.90 | 9.66 | 9.50 | 9.39 | 9.26 | 9.12 | 8.99 | 8.96 | 9.45 | 10.17 | 9.86 | 9.75 | 9.59 | 9.35 |
| 5 | 11.67 | 11.49 | 11.40 | 12.60 | 12.47 | 12.31 | 12.13 | 12.06 | 12.73 | 13.70 | 13.26 | 13.10 | 12.87 | 12.53 |
| 6 | 14.38 | 14.37 | 14.38 | 16.00 | 15.91 | 15.76 | 15.56 | 15.47 | 16.33 | 17.57 | 16.98 | 16.76 | 16.45 | 15.98 |
| 7 | 16.99 | 17.18 | 17.36 | 19.47 | 19.48 | 19.38 | 19.20 | 19.09 | 20.17 | 21.71 | 20.98 | 20.71 | 20.31 | 19.68 |
| 8 | 19.46 | 19.91 | 20.23 | 22.86 | 23.03 | 23.03 | 22.91 | 22.84 | 24.14 | 26.02 | 25.18 | 24.85 | 24.38 | 23.61 |
| 9 | 24.03 | 24.79 | 25.50 | 26.16 | 26.57 | 26.72 | 26.69 | 26.68 | 28.22 | 30.47 | 29.55 | 29.18 | 28.63 | 27.75 |
| 10 | 26.24 | 27.30 | 28.27 | 29.14 | 29.71 | 30.05 | 30.22 | 30.39 | 32.24 | 34.93 | 33.99 | 33.58 | 32.98 | 31.99 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.65 | 8.42 | 8.28 | 8.20 | 8.10 | 8.00 | 7.91 | 7.90 | 8.36 | 9.01 | 8.76 | 8.67 | 8.54 | 8.35 |
| 5 | 10.12 | 9.95 | 9.85 | 10.88 | 10.78 | 10.65 | 10.51 | 10.48 | 11.08 | 11.94 | 11.58 | 11.45 | 11.27 | 11.00 |
| 6 | 12.51 | 12.41 | 12.34 | 13.71 | 13.63 | 13.50 | 13.35 | 13.29 | 14.04 | 15.12 | 14.64 | 14.47 | 14.22 | 13.83 |
| 7 | 14.82 | 14.84 | 14.90 | 16.64 | 16.61 | 16.50 | 16.34 | 16.27 | 17.19 | 18.52 | 17.92 | 17.70 | 17.37 | 16.86 |
| 8 | 17.04 | 17.24 | 17.43 | 19.59 | 19.65 | 19.59 | 19.46 | 19.38 | 20.48 | 22.08 | 21.37 | 21.10 | 20.68 | 20.04 |
| 9 | 21.28 | 21.73 | 22.15 | 22.46 | 22.64 | 22.68 | 22.59 | 22.55 | 23.84 | 25.72 | 24.93 | 24.61 | 24.13 | 23.36 |
| 10 | 23.46 | 24.08 | 24.74 | 25.34 | 25.65 | 25.79 | 25.77 | 25.78 | 27.28 | 29.45 | 28.59 | 28.23 | 27.69 | 26.81 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 33.986 | 28.588 |
| SC2 | 0 | 8 | 22.840 | 19.377 |
| SC3 | -18 | 7 | 19.490 | 16.641 |
| SC4 | -25 | 6 | 14.380 | 12.341 |
| SC5 | -34 | 6 | 14.400 | 12.506 |
| A | 1725 mm |
|---|---|
| B | 1000 mm |
| C | 1150 mm |
| F | 960 mm |
| G | 1540 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1725 mm |
|---|---|
| Width | 1540 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.