EK-DI-263AC10-A13 C
31.58 kW
Defrost: None
Product code: EK-DI-163AI10-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,176 m³/h |
|---|---|
| External surface | 132.3 m² |
| Inner volume | 56.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 291 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.5 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EK-DI-163AI10-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.19 | 14.73 | 14.45 | 14.30 | 14.13 | 13.96 | 13.79 | 13.85 | 14.67 | 15.85 | 15.45 | 15.31 | 15.09 | 14.77 |
| 5 | 17.78 | 17.35 | 17.10 | 18.84 | 18.64 | 18.41 | 18.16 | 18.15 | 19.20 | 20.71 | 20.11 | 19.89 | 19.59 | 19.14 |
| 6 | 21.95 | 21.58 | 21.38 | 23.65 | 23.45 | 23.19 | 22.87 | 22.80 | 24.10 | 25.96 | 25.14 | 24.83 | 24.40 | 23.75 |
| 7 | 26.16 | 25.91 | 25.80 | 28.63 | 28.47 | 28.21 | 27.86 | 27.74 | 29.30 | 31.55 | 30.50 | 30.10 | 29.53 | 28.64 |
| 8 | 30.22 | 30.16 | 30.22 | 33.71 | 33.64 | 33.39 | 33.04 | 32.88 | 34.73 | 37.41 | 36.14 | 35.65 | 34.93 | 33.79 |
| 9 | 37.93 | 38.16 | 38.47 | 38.80 | 38.85 | 38.67 | 38.34 | 38.18 | 40.33 | 43.44 | 42.00 | 41.41 | 40.56 | 39.16 |
| 10 | 42.10 | 42.69 | 43.29 | 43.87 | 43.99 | 43.95 | 43.68 | 43.57 | 46.03 | 49.60 | 47.99 | 47.33 | 46.34 | 44.73 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.77 | 12.40 | 12.19 | 12.10 | 11.99 | 11.87 | 11.74 | 11.89 | 12.62 | 13.67 | 13.36 | 13.25 | 13.10 | 12.88 |
| 5 | 14.83 | 14.46 | 14.26 | 15.74 | 15.59 | 15.42 | 15.23 | 15.32 | 16.23 | 17.54 | 17.06 | 16.89 | 16.66 | 16.31 |
| 6 | 18.24 | 17.88 | 17.69 | 19.57 | 19.41 | 19.20 | 18.95 | 18.98 | 20.08 | 21.67 | 21.00 | 20.75 | 20.40 | 19.87 |
| 7 | 21.66 | 21.35 | 21.21 | 23.53 | 23.39 | 23.16 | 22.86 | 22.83 | 24.13 | 26.03 | 25.16 | 24.83 | 24.35 | 23.61 |
| 8 | 25.10 | 24.87 | 24.78 | 27.58 | 27.48 | 27.25 | 26.91 | 26.84 | 28.36 | 30.56 | 29.51 | 29.09 | 28.49 | 27.52 |
| 9 | 31.58 | 31.48 | 31.55 | 31.70 | 31.63 | 31.41 | 31.07 | 30.98 | 32.71 | 35.23 | 34.02 | 33.52 | 32.79 | 31.59 |
| 10 | 35.16 | 35.27 | 35.51 | 35.81 | 35.82 | 35.65 | 35.30 | 35.21 | 37.18 | 40.02 | 38.66 | 38.08 | 37.22 | 35.80 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 47.989 | 38.662 |
| SC2 | 0 | 8 | 32.883 | 26.844 |
| SC3 | -18 | 7 | 28.578 | 23.487 |
| SC4 | -25 | 6 | 21.384 | 17.691 |
| SC5 | -34 | 6 | 21.895 | 18.181 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1150 mm |
| F | 1160 mm |
| G | 1740 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø66,7 |
| Length | 1725 mm |
|---|---|
| Width | 1740 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.