EK-K-b-663BG10-B29 C
123.37 kW
Defrost: None
Product code: EK-K-s-663BG10-B08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 82,838 m³/h |
|---|---|
| External surface | 439.5 m² |
| Inner volume | 183.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 895 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 11,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 76.0 dB(A) |
|---|---|
| Sound power | 100.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø80 |
| EK-K-s-663BG10-B08 C | None |
|---|---|
| EK-K-s-663BG10-B08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 55.86 | 53.85 | 52.58 | 51.80 | 51.00 | 50.19 | 49.41 | 50.04 | 52.87 | 57.02 | 55.50 | 54.95 | 54.17 | 53.03 |
| 5 | 66.45 | 64.49 | 63.22 | 69.32 | 68.23 | 67.05 | 65.81 | 66.15 | 70.05 | 75.50 | 73.28 | 72.52 | 71.48 | 69.96 |
| 6 | 83.28 | 81.30 | 80.16 | 88.23 | 87.02 | 85.57 | 83.93 | 83.95 | 88.74 | 95.50 | 92.25 | 91.12 | 89.54 | 87.23 |
| 7 | 100.00 | 98.61 | 97.80 | 108.03 | 106.91 | 105.34 | 103.41 | 103.13 | 108.88 | 117.07 | 112.75 | 111.18 | 108.96 | 105.57 |
| 8 | 116.44 | 115.78 | 115.60 | 128.45 | 127.58 | 125.99 | 123.90 | 123.37 | 130.17 | 139.97 | 134.59 | 132.58 | 129.66 | 125.09 |
| 9 | 147.04 | 147.48 | 148.21 | 148.99 | 148.59 | 147.26 | 145.15 | 144.41 | 152.36 | 163.87 | 157.57 | 155.03 | 151.43 | 145.66 |
| 10 | 163.99 | 165.86 | 167.36 | 169.16 | 169.34 | 168.45 | 166.54 | 165.92 | 175.08 | 188.32 | 181.29 | 178.41 | 174.19 | 167.36 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 48.30 | 46.64 | 45.66 | 45.13 | 44.57 | 44.00 | 43.42 | 44.09 | 46.85 | 50.62 | 49.41 | 48.97 | 48.35 | 47.42 |
| 5 | 56.95 | 55.24 | 54.21 | 59.56 | 58.78 | 57.92 | 57.00 | 57.45 | 60.89 | 65.76 | 63.95 | 63.34 | 62.49 | 61.27 |
| 6 | 70.90 | 69.18 | 68.16 | 75.06 | 74.15 | 73.05 | 71.80 | 71.98 | 76.16 | 82.09 | 79.44 | 78.52 | 77.22 | 75.31 |
| 7 | 85.17 | 83.48 | 82.63 | 91.30 | 90.38 | 89.13 | 87.61 | 87.51 | 92.46 | 99.56 | 96.04 | 94.76 | 92.93 | 90.13 |
| 8 | 99.22 | 98.04 | 97.49 | 108.02 | 107.21 | 105.92 | 104.21 | 103.86 | 109.64 | 118.01 | 113.62 | 111.96 | 109.55 | 105.78 |
| 9 | 125.57 | 124.90 | 124.86 | 125.09 | 124.51 | 123.21 | 121.41 | 120.87 | 127.54 | 137.21 | 132.06 | 130.00 | 127.02 | not rated |
| 10 | 140.45 | 140.67 | 141.35 | 142.19 | 141.85 | 140.77 | 138.95 | 138.37 | 145.99 | 156.99 | 151.17 | 148.74 | 145.19 | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 181.290 | 151.171 |
| SC2 | 0 | 8 | 123.365 | 103.862 |
| SC3 | -18 | 7 | 107.647 | 90.978 |
| SC4 | -25 | 6 | 80.160 | 68.159 |
| SC5 | -34 | 6 | 82.799 | 70.602 |
| A | 3460 mm |
|---|---|
| B | 1150 mm |
| C | 1935 mm |
| F | 940 mm |
| G | 3035 mm |
| E | 2050 mm |
| G1 | 1035 mm |
| G2 | 1000 mm |
| D IN | 2 x Ø35 |
| D OUT | 2 x Ø80 |
| Length | 3460 mm |
|---|---|
| Width | 1150 mm |
| Height | 2050 mm |
Our engineers answer with a selection for your conditions.