EK-S-250AG10-B10 C
26.18 kW
Defrost: None
Product code: EK-S-163BG10-B08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 15,379 m³/h |
|---|---|
| External surface | 97.7 m² |
| Inner volume | 41.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 341 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EK-S-163BG10-B08 C | None |
|---|---|
| EK-S-163BG10-B08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.20 | 10.82 | 10.59 | 10.46 | 10.33 | 10.20 | 10.08 | 10.14 | 10.75 | 11.60 | 11.31 | 11.20 | 11.05 | 10.82 |
| 5 | 13.23 | 12.85 | 12.62 | 13.86 | 13.68 | 13.49 | 13.30 | 13.31 | 14.09 | 15.20 | 14.77 | 14.62 | 14.41 | 14.10 |
| 6 | 16.46 | 16.11 | 15.89 | 17.52 | 17.32 | 17.09 | 16.83 | 16.78 | 17.74 | 19.10 | 18.49 | 18.28 | 17.97 | 17.51 |
| 7 | 19.77 | 19.47 | 19.29 | 21.34 | 21.16 | 20.91 | 20.60 | 20.50 | 21.65 | 23.31 | 22.51 | 22.22 | 21.81 | 21.17 |
| 8 | 22.99 | 22.82 | 22.76 | 25.29 | 25.13 | 24.89 | 24.57 | 24.43 | 25.79 | 27.76 | 26.79 | 26.42 | 25.89 | 25.05 |
| 9 | 29.02 | 29.04 | 29.14 | 29.28 | 29.21 | 29.01 | 28.67 | 28.51 | 30.10 | 32.40 | 31.27 | 30.82 | 30.18 | 29.12 |
| 10 | 32.37 | 32.65 | 32.96 | 33.27 | 33.30 | 33.16 | 32.86 | 32.72 | 34.53 | 37.16 | 35.89 | 35.38 | 34.62 | 33.34 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.72 | 9.41 | 9.23 | 9.14 | 9.05 | 8.96 | 8.87 | 8.97 | 9.53 | 10.31 | 10.09 | 10.00 | 9.88 | 9.70 |
| 5 | 11.39 | 11.06 | 10.87 | 11.97 | 11.84 | 11.70 | 11.55 | 11.61 | 12.31 | 13.30 | 12.95 | 12.82 | 12.66 | 12.41 |
| 6 | 14.11 | 13.78 | 13.59 | 14.99 | 14.84 | 14.66 | 14.45 | 14.47 | 15.31 | 16.51 | 16.01 | 15.83 | 15.58 | 15.20 |
| 7 | 16.87 | 16.56 | 16.40 | 18.14 | 17.99 | 17.78 | 17.53 | 17.50 | 18.50 | 19.94 | 19.28 | 19.03 | 18.69 | 18.15 |
| 8 | 19.66 | 19.41 | 19.27 | 21.39 | 21.26 | 21.04 | 20.76 | 20.69 | 21.85 | 23.54 | 22.72 | 22.41 | 21.96 | 21.25 |
| 9 | 24.86 | 24.69 | 24.67 | 24.71 | 24.60 | 24.40 | 24.10 | 24.00 | 25.33 | 27.28 | 26.33 | 25.94 | 25.39 | 24.50 |
| 10 | 27.79 | 27.78 | 27.89 | 28.05 | 28.00 | 27.81 | 27.51 | 27.40 | 28.93 | 31.13 | 30.06 | 29.61 | 28.95 | 27.89 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 35.893 | 30.055 |
| SC2 | 0 | 8 | 24.432 | 20.688 |
| SC3 | -18 | 7 | 21.280 | 18.089 |
| SC4 | -25 | 6 | 15.893 | 13.586 |
| SC5 | -34 | 6 | 16.405 | 14.052 |
| A | 1460 mm |
|---|---|
| B | 1180 mm |
| C | 2230 mm |
| F | 700 mm |
| G | 1065 mm |
| E | 2470 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 1460 mm |
|---|---|
| Width | 1180 mm |
| Height | 2470 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.