EK-S-163BG10-B13 C
27.41 kW
Defrost: None
Product code: EK-S-250AG10-B10 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 14,724 m³/h |
|---|---|
| External surface | 117.2 m² |
| Inner volume | 49.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 379 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 1,380 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 83.1 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EK-S-250AG10-B10 C | None |
|---|---|
| EK-S-250AG10-B10 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.23 | 11.84 | 11.62 | 11.50 | 11.38 | 11.26 | 11.14 | 11.22 | 11.90 | 12.87 | 12.57 | 12.47 | 12.30 | 12.06 |
| 5 | 14.31 | 13.92 | 13.70 | 15.09 | 14.93 | 14.76 | 14.57 | 14.60 | 15.46 | 16.70 | 16.23 | 16.07 | 15.85 | 15.51 |
| 6 | 17.69 | 17.32 | 17.12 | 18.91 | 18.73 | 18.52 | 18.27 | 18.26 | 19.30 | 20.82 | 20.17 | 19.94 | 19.61 | 19.11 |
| 7 | 21.14 | 20.78 | 20.64 | 22.87 | 22.72 | 22.49 | 22.20 | 22.13 | 23.38 | 25.20 | 24.37 | 24.06 | 23.62 | 22.93 |
| 8 | 24.51 | 24.30 | 24.24 | 26.93 | 26.82 | 26.60 | 26.29 | 26.18 | 27.66 | 29.80 | 28.79 | 28.40 | 27.83 | 26.94 |
| 9 | 30.90 | 30.83 | 30.91 | 31.06 | 31.02 | 30.80 | 30.49 | 30.38 | 32.08 | 34.55 | 33.39 | 32.92 | 32.24 | 31.14 |
| 10 | 34.44 | 34.61 | 34.88 | 35.19 | 35.22 | 35.09 | 34.79 | 34.67 | 36.62 | 39.44 | 38.14 | 37.59 | 36.80 | 35.49 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.69 | 10.37 | 10.19 | 10.12 | 10.04 | 9.95 | 9.85 | 9.97 | 10.59 | 11.47 | 11.22 | 11.13 | 11.02 | 10.85 |
| 5 | 12.43 | 12.09 | 11.91 | 13.14 | 13.03 | 12.90 | 12.75 | 12.82 | 13.59 | 14.69 | 14.30 | 14.17 | 13.98 | 13.70 |
| 6 | 15.31 | 14.97 | 14.78 | 16.34 | 16.21 | 16.04 | 15.85 | 15.87 | 16.80 | 18.13 | 17.59 | 17.40 | 17.12 | 16.70 |
| 7 | 18.23 | 17.90 | 17.75 | 19.66 | 19.53 | 19.35 | 19.11 | 19.09 | 20.18 | 21.77 | 21.07 | 20.81 | 20.43 | 19.84 |
| 8 | 21.17 | 20.86 | 20.77 | 23.07 | 22.96 | 22.77 | 22.51 | 22.44 | 23.71 | 25.57 | 24.72 | 24.39 | 23.90 | 23.14 |
| 9 | 26.72 | 26.51 | 26.48 | 26.53 | 26.46 | 26.27 | 25.99 | 25.91 | 27.37 | 29.49 | 28.50 | 28.10 | 27.52 | 26.57 |
| 10 | 29.83 | 29.77 | 29.86 | 30.03 | 30.00 | 29.83 | 29.55 | 29.47 | 31.12 | 33.52 | 32.41 | 31.94 | 31.25 | 30.12 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 38.136 | 32.406 |
| SC2 | 0 | 8 | 26.183 | 22.444 |
| SC3 | -18 | 7 | 22.819 | 19.619 |
| SC4 | -25 | 6 | 17.116 | 14.784 |
| SC5 | -34 | 6 | 17.629 | 15.252 |
| A | 2060 mm |
|---|---|
| B | 1100 mm |
| C | 1930 mm |
| F | 700 mm |
| G | 1665 mm |
| E | 2170 mm |
| G1 | 833 mm |
| G2 | 800 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2060 mm |
|---|---|
| Width | 1100 mm |
| Height | 2170 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.