EK-SR-480BC4-A05 C
108.25 kW
Defrost: None
Product code: EK-SR-380BE4-A05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 69,240 m³/h |
|---|---|
| External surface | 586.4 m² |
| Inner volume | 117.5 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 1,027 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 1,310 rpm |
| Power | 11,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 97.2 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EK-SR-380BE4-A05 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 43.81 | 45.57 | 47.03 | 48.16 | 48.44 | 48.54 | 48.33 | 48.92 | 51.96 | 56.22 | 54.84 | 54.30 | 53.51 | 52.30 |
| 5 | 47.97 | 51.01 | ≈ 53.48 | ≈ 61.80 | 63.36 | 64.18 | 64.28 | 65.08 | 69.11 | 74.83 | 72.93 | 72.23 | 71.22 | 69.68 |
| 6 | 55.54 | 59.55 | 63.19 | ≈ 73.72 | 76.16 | 77.70 | 78.53 | 79.78 | 84.87 | 92.24 | 90.40 | 89.66 | 88.57 | 86.79 |
| 7 | ≈ 62.08 | 67.44 | ≈ 72.39 | ≈ 85.26 | 88.73 | 91.05 | 92.41 | 93.97 | 99.99 | 108.77 | 106.62 | 105.74 | 104.39 | 102.14 |
| 8 | ≈ 67.90 | 74.66 | ≈ 81.01 | ≈ 96.29 | 100.98 | 104.23 | 106.26 | 108.24 | 115.24 | 125.48 | 123.11 | 122.10 | 120.52 | 117.82 |
| 9 | ≈ 54.03 | ≈ 90.25 | 98.91 | 106.78 | 112.81 | 117.15 | 119.99 | 122.50 | 130.52 | 142.27 | 139.78 | 138.65 | 136.87 | 133.73 |
| 10 | ≈ 33.83 | ≈ 96.83 | 107.17 | 116.68 | 124.18 | 129.69 | 133.46 | 136.69 | 145.76 | 159.03 | 156.54 | 155.33 | 153.39 | 149.83 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 39.35 | 40.42 | 41.33 | 42.06 | 42.35 | 42.28 | 42.05 | 42.61 | 45.27 | 49.01 | 47.88 | 47.48 | 46.88 | 45.90 |
| 5 | 43.83 | 45.89 | 47.32 | 54.18 | 55.07 | 55.41 | 55.32 | 55.93 | 59.36 | 64.27 | 62.61 | 61.98 | 61.12 | 59.81 |
| 6 | 50.98 | 53.98 | 56.69 | ≈ 65.61 | 67.37 | 68.44 | 68.95 | 69.92 | 74.30 | 80.51 | 78.42 | 77.61 | 76.40 | 74.48 |
| 7 | 57.26 | 61.39 | ≈ 65.15 | ≈ 76.03 | 78.57 | 80.18 | 81.05 | 82.21 | 87.39 | 94.98 | 92.95 | 92.12 | 90.87 | 88.80 |
| 8 | ≈ 62.93 | 68.25 | ≈ 73.17 | ≈ 86.10 | 89.54 | 91.85 | 93.17 | 94.60 | 100.60 | 109.41 | 107.10 | 106.13 | 104.65 | 102.13 |
| 9 | ≈ 75.57 | 82.86 | 89.68 | 95.75 | 100.25 | 103.31 | 105.21 | 107.02 | 113.87 | 123.89 | 121.43 | 120.33 | 118.63 | 115.69 |
| 10 | ≈ 75.09 | ≈ 89.27 | 97.52 | 104.96 | 110.57 | 114.56 | 117.14 | 119.42 | 127.14 | 138.42 | 135.88 | 134.67 | 132.78 | 129.44 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 156.544 | 135.875 |
| SC2 | 0 | 8 | 108.238 | 94.596 |
| SC3 | -18 | 7 | 86.799 | 77.161 |
| SC4 | -25 | 6 | 63.190 | 56.694 |
| SC5 | -34 | 6 | 56.456 | 51.678 |
| A | 4360 mm |
|---|---|
| B | 1360 mm |
| C | 2790 mm |
| F | 1310 mm |
| G | 1770 mm |
| E | 3965 mm |
| H | 1393 mm |
| I | 4390 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 4360 mm |
|---|---|
| Width | 1393 mm |
| Height | 2790 mm |
Our engineers answer with a selection for your conditions.