EK-T-463BG10-B08 C
81.98 kW
Defrost: None
Product code: EK-T-291AG10-B04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 47,747 m³/h |
|---|---|
| External surface | 253.9 m² |
| Inner volume | 103.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 519 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 94.1 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EK-T-291AG10-B04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 34.33 | 33.64 | 33.19 | 32.89 | 32.45 | 31.93 | 31.35 | 31.79 | 33.71 | 36.30 | 35.23 | 34.83 | 34.27 | 33.42 |
| 5 | 40.20 | 39.84 | 39.57 | 43.84 | 43.43 | 42.81 | 42.05 | 42.34 | 44.85 | 48.34 | 46.79 | 46.27 | 45.54 | 44.45 |
| 6 | 49.21 | 49.37 | 49.58 | 55.31 | 55.06 | 54.43 | 53.58 | 53.73 | 56.83 | 61.20 | 59.03 | 58.25 | 57.14 | 55.45 |
| 7 | 57.84 | 58.71 | 59.51 | 66.87 | 66.84 | 66.41 | 65.59 | 65.65 | 69.37 | 74.74 | 72.03 | 71.00 | 69.49 | 67.11 |
| 8 | 65.98 | 67.44 | 68.99 | 78.10 | 78.70 | 78.58 | 77.91 | 77.97 | 82.41 | 88.88 | 85.70 | 84.44 | 82.56 | 79.55 |
| 9 | 80.94 | 83.69 | 86.24 | 88.51 | 89.85 | 90.37 | 90.28 | 90.51 | 95.71 | 103.26 | 99.77 | 98.30 | 96.12 | 92.53 |
| 10 | 88.26 | 92.04 | 95.46 | 98.48 | 100.24 | 101.15 | 101.30 | 102.01 | 108.09 | 116.94 | 113.71 | 112.31 | 109.90 | 105.77 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 28.11 | 27.46 | 27.08 | 26.86 | 26.56 | 26.19 | not rated | 26.30 | 27.98 | 30.27 | 29.56 | 29.33 | 28.95 | 28.34 |
| 5 | 32.66 | 32.18 | 31.92 | 35.31 | 34.98 | 34.51 | not rated | 34.31 | 36.38 | 39.29 | 38.10 | 37.70 | 37.15 | 36.38 |
| 6 | 40.14 | 39.86 | 39.72 | 44.15 | 43.87 | 43.35 | not rated | 42.87 | 45.37 | 48.92 | 47.22 | 46.61 | 45.74 | not rated |
| 7 | 47.36 | 47.45 | 47.67 | 53.24 | 53.09 | 52.56 | not rated | 51.87 | 54.82 | 59.09 | not rated | not rated | not rated | not rated |
| 8 | 54.31 | 54.91 | 55.53 | 62.35 | 62.43 | 62.02 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | 67.73 | 69.06 | 70.32 | 71.26 | 71.60 | 71.38 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | 74.65 | 76.50 | 78.47 | 80.17 | 80.87 | 80.88 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 113.714 | — |
| SC2 | 0 | 8 | 77.970 | — |
| SC3 | -18 | 7 | 66.980 | 53.226 |
| SC4 | -25 | 6 | 49.583 | 39.715 |
| SC5 | -34 | 6 | 49.315 | 40.126 |
| A | 3038 mm |
|---|---|
| C | 1287 mm |
| F | 1032 mm |
| G | 1150 mm |
| E1 | 1335 mm |
| E2 | 1300 mm |
| E | 2635 mm |
| H | 1354 mm |
| I | 1465 mm |
| D IN | 2 x Ø35 |
| D OUT | 2 x Ø54 |
| Length | 3038 mm |
|---|---|
| Width | 1354 mm |
| Height | 1465 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.