EK-T-291AG10-B04 C
77.97 kW
Defrost: None
Product code: EK-T-463BG10-B08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 55,121 m³/h |
|---|---|
| External surface | 293.0 m² |
| Inner volume | 120.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 630 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 7,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 98.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| EK-T-463BG10-B08 C | None |
|---|---|
| EK-T-463BG10-B08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 36.03 | 35.15 | 34.55 | 34.16 | 33.66 | 33.10 | 32.52 | 32.88 | 34.76 | 37.43 | 36.32 | 35.92 | 35.34 | 34.49 |
| 5 | 42.48 | 41.78 | 41.42 | 45.75 | 45.22 | 44.53 | 43.72 | 43.92 | 46.49 | 50.08 | 48.50 | 47.96 | 47.19 | 46.08 |
| 6 | 52.35 | 52.21 | 52.20 | 58.02 | 57.57 | 56.87 | 55.92 | 55.99 | 59.18 | 63.69 | 61.46 | 60.66 | 59.53 | 57.84 |
| 7 | 61.87 | 62.44 | 62.98 | 70.51 | 70.41 | 69.82 | 68.85 | 68.77 | 72.66 | 78.21 | 75.36 | 74.29 | 72.74 | 70.30 |
| 8 | 70.92 | 72.36 | 73.39 | 82.77 | 83.16 | 82.87 | 82.03 | 81.98 | 86.61 | 93.32 | 89.90 | 88.58 | 86.64 | 83.53 |
| 9 | 87.59 | 90.10 | 92.48 | 94.63 | 95.88 | 96.11 | 95.49 | 95.51 | 100.96 | 108.86 | 105.09 | 103.55 | 101.26 | 97.52 |
| 10 | 95.76 | 99.32 | 102.58 | 105.48 | 107.15 | 108.01 | 108.10 | 108.75 | 115.22 | 124.61 | 120.53 | 118.79 | 116.20 | 111.89 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 31.17 | 30.34 | 29.84 | 29.54 | 29.18 | 28.77 | 28.33 | 28.72 | 30.49 | 32.93 | 32.06 | 31.74 | 31.28 | 30.60 |
| 5 | 36.47 | 35.82 | 35.43 | 39.12 | 38.70 | 38.16 | 37.53 | 37.78 | 40.03 | 43.19 | 41.90 | 41.46 | 40.85 | 39.96 |
| 6 | 45.06 | 44.62 | 44.36 | 49.21 | 48.85 | 48.25 | 47.48 | 47.60 | 50.34 | 54.24 | 52.41 | 51.76 | 50.83 | 49.43 |
| 7 | 53.39 | 53.36 | 53.50 | 59.66 | 59.38 | 58.83 | 57.98 | 57.97 | 61.26 | 65.99 | 63.63 | 62.74 | 61.46 | 59.45 |
| 8 | 61.41 | 61.97 | 62.57 | 70.16 | 70.19 | 69.74 | 68.90 | 68.77 | 72.65 | 78.28 | 75.42 | 74.30 | 72.66 | 70.02 |
| 9 | 76.76 | 78.16 | 79.48 | 80.45 | 80.87 | 80.61 | 79.88 | 79.82 | 84.32 | 90.83 | 87.59 | 86.26 | 84.31 | not rated |
| 10 | 84.71 | 86.69 | 88.83 | 90.74 | 91.53 | 91.61 | 91.02 | 91.07 | 96.24 | 103.70 | 100.16 | 98.64 | 96.39 | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 120.532 | 100.160 |
| SC2 | 0 | 8 | 81.975 | 68.774 |
| SC3 | -18 | 7 | 70.539 | 59.612 |
| SC4 | -25 | 6 | 52.202 | 44.356 |
| SC5 | -34 | 6 | 52.393 | 45.020 |
| A | 4460 mm |
|---|---|
| B | 1200 mm |
| C | 1035 mm |
| F | 940 mm |
| G | 4035 mm |
| E | 1150 mm |
| G1 | 1035 mm |
| G2 | 1000 mm |
| D IN | 2 x Ø42 |
| D OUT | 2 x Ø54 |
| Length | 4460 mm |
|---|---|
| Width | 1200 mm |
| Height | 1150 mm |