Skip to Content

Brine cooler EA-G-150AG4-A10 C

Brine cooler EA-G-150AG4-A10 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-150AG4-A10 C

Cooling capacity i
14.16 kW
Air flow
5,499 m³/h
Fin spacing
4.2 mm
Air throw
15 m
Fans
1 × ⌀500 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 5,499 m³/h
Air throw 15 m
External surface 69.0 m²
Inner volume 16.3 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 86 kg
Fans
Quantity 1
Diameter 500 mm
Speed 1,360 rpm
Power 690 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 83.0 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
EA-G-150AG4-A10 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
14.159 kW Sensible capacity 10.166 kW Fluid flow 4.44 m³/h Pressure drop 67.7 kPa
Cooling capacity · Low speed (Y)
10.189 kW Sensible capacity 7.326 kW Fluid flow 3.20 m³/h Pressure drop 37.9 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 5.29 4.67 ≈ 4.64 ≈ 4.62
8 not rated not rated not rated not rated 8.42 ≈ 8.03 ≈ 9.79 ≈ 11.88
10 not rated not rated not rated not rated ≈ 11.57 14.16 15.86 17.67
12 not rated not rated not rated not rated not rated 18.99 20.91 23.03

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 4.77 4.25 4.13 4.06
8 not rated not rated not rated not rated 7.49 7.18 7.00 not rated
10 not rated not rated not rated not rated 10.20 10.19 ≈ 13.07 not rated
12 not rated not rated not rated not rated not rated 15.46 not rated not rated

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 14.159 4.44 67.7
Low speed (Y) 10.189 3.20 37.9

Dimensions

Dimension drawing of EA-G-150AG4-A10 C
Dimension drawing
Dimensions as drawn
A 1237 mm
B 740 mm
C 685 mm
F 545 mm
E 885 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 1237 mm
Width 740 mm
Height 685 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.