EA-G-150BG7-A10 C
14.24 kW
Defrost: None
Product code: EA-G-163EG10-A06 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 7,981 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 64.9 m² |
| Inner volume | 30.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 129 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.6 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-163EG10-A06 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 5.74 | 5.09 | ≈ 4.94 | ≈ 4.90 |
| 8 | not rated | not rated | not rated | not rated | 9.00 | ≈ 8.58 | ≈ 10.22 | ≈ 11.48 |
| 10 | not rated | not rated | not rated | not rated | ≈ 12.34 | 14.20 | 15.39 | 16.89 |
| 12 | not rated | not rated | not rated | not rated | not rated | 18.67 | 20.16 | 21.96 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 5.09 | 4.57 | 4.45 | ≈ 4.30 |
| 8 | not rated | not rated | not rated | not rated | 7.90 | 7.60 | ≈ 7.83 | ≈ 9.56 |
| 10 | not rated | not rated | not rated | not rated | 10.70 | 11.55 | 12.82 | 14.13 |
| 12 | not rated | not rated | not rated | not rated | not rated | 15.42 | 16.82 | 18.36 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 14.204 | 4.46 | 62.0 |
| Low speed (Y) | 11.546 | 3.63 | 43.0 |
| A | 1215 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E | 835 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 1215 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.