EA-G-250BE4-A10 C
27.81 kW
Defrost: None
Product code: EA-G-263ED4-A06 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 16,221 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 167.1 m² |
| Inner volume | 37.1 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 189 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.4 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263ED4-A06 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 7.91 | 7.31 | ≈ 7.35 | ≈ 7.35 |
| 8 | not rated | not rated | not rated | not rated | 13.04 | ≈ 12.10 | ≈ 19.53 | ≈ 21.90 |
| 10 | not rated | not rated | not rated | not rated | 24.55 | 27.70 | 30.10 | 33.35 |
| 12 | not rated | not rated | not rated | not rated | not rated | 37.21 | 40.23 | 44.07 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 7.32 | 6.67 | ≈ 6.69 | ≈ 6.66 |
| 8 | not rated | not rated | not rated | not rated | 11.93 | ≈ 11.16 | ≈ 15.73 | ≈ 18.49 |
| 10 | not rated | not rated | not rated | not rated | ≈ 16.67 | 22.87 | 25.39 | 28.28 |
| 12 | not rated | not rated | not rated | not rated | not rated | 31.14 | 34.01 | 37.32 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 27.702 | 8.70 | 56.4 |
| Low speed (Y) | 22.871 | 7.18 | 40.2 |
| A | 2015 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2015 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.