EA-G-263FG10-A08 C
43.02 kW
Defrost: None
Product code: EA-G-263EE4-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 27,672 m³/h |
|---|---|
| Air throw | 37 m |
| External surface | 200.5 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 201 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 93.4 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263EE4-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 10.54 | ≈ 10.02 | ≈ 10.09 | ≈ 15.30 |
| 8 | not rated | not rated | not rated | not rated | ≈ 17.64 | ≈ 26.89 | ≈ 30.67 | ≈ 33.22 |
| 10 | not rated | not rated | not rated | not rated | ≈ 40.31 | 43.03 | 45.82 | 50.26 |
| 12 | not rated | not rated | not rated | not rated | not rated | 57.25 | 61.09 | 66.43 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.88 | ≈ 9.21 | ≈ 9.26 | ≈ 9.27 |
| 8 | not rated | not rated | not rated | not rated | ≈ 16.35 | ≈ 21.33 | ≈ 25.64 | ≈ 28.60 |
| 10 | not rated | not rated | not rated | not rated | ≈ 33.22 | 36.46 | 39.30 | 43.36 |
| 12 | not rated | not rated | not rated | not rated | not rated | 48.72 | 52.43 | 57.23 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 43.034 | 13.51 | 91.2 |
| Low speed (Y) | 36.456 | 11.45 | 67.9 |
| A | 2015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.