Skip to Content

Brine cooler EA-G-263FG7-A19 C

Brine cooler EA-G-263FG7-A19 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-263FG7-A19 C

Cooling capacity i
42.65 kW
Air flow
21,897 m³/h
Fin spacing
7.0 mm
Air throw
28 m
Fans
2 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 21,897 m³/h
Air throw 28 m
External surface 225.3 m²
Inner volume 72.6 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 254 kg
Fans
Quantity 2
Diameter 630 mm
Speed 1,330 rpm
Power 2,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 63.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-263FG7-A19 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
42.652 kW Sensible capacity 30.817 kW Fluid flow 13.39 m³/h Pressure drop 62.6 kPa
Cooling capacity · Low speed (Y)
36.257 kW Sensible capacity 26.141 kW Fluid flow 11.39 m³/h Pressure drop 47.0 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 13.31 12.00 ≈ 12.03 ≈ 12.01
8 not rated not rated not rated not rated 21.52 ≈ 20.11 ≈ 30.69 ≈ 34.06
10 not rated not rated not rated not rated 39.11 42.65 45.88 50.33
12 not rated not rated not rated not rated not rated 56.11 60.31 65.67

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 12.32 10.93 ≈ 10.94 ≈ 10.91
8 not rated not rated not rated not rated 19.72 ≈ 18.56 ≈ 25.92 ≈ 29.39
10 not rated not rated not rated not rated ≈ 27.22 36.26 39.54 43.50
12 not rated not rated not rated not rated not rated 48.05 52.01 56.66

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 42.652 13.39 62.6
Low speed (Y) 36.257 11.39 47.0

Dimensions

Dimension drawing of EA-G-263FG7-A19 C
Dimension drawing
Dimensions as drawn
A 2415 mm
B 1100 mm
C 1190 mm
F 1060 mm
E1 1018 mm
E 2035 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2415 mm
Width 1100 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.