EA-G-250AG7-A10 C
26.00 kW
Defrost: None
Product code: EA-G-263FD10-A19 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 24,062 m³/h |
|---|---|
| Air throw | 30 m |
| External surface | 101.7 m² |
| Inner volume | 45.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 198 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263FD10-A19 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.15 | 7.34 | ≈ 7.36 | ≈ 7.36 |
| 8 | not rated | not rated | not rated | not rated | 13.22 | ≈ 12.35 | ≈ 18.87 | ≈ 20.74 |
| 10 | not rated | not rated | not rated | not rated | 23.78 | 26.05 | 28.11 | 30.93 |
| 12 | not rated | not rated | not rated | not rated | not rated | 34.44 | 37.08 | 40.51 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 7.63 | 6.79 | ≈ 6.80 | ≈ 6.79 |
| 8 | not rated | not rated | not rated | not rated | 12.29 | ≈ 11.54 | ≈ 16.55 | ≈ 18.39 |
| 10 | not rated | not rated | not rated | not rated | ≈ 17.04 | 22.78 | 24.90 | 27.53 |
| 12 | not rated | not rated | not rated | not rated | not rated | 30.36 | 32.91 | 36.04 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 26.045 | 8.18 | 60.8 |
| Low speed (Y) | 22.779 | 7.15 | 47.9 |
| A | 2415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 1018 mm |
| E | 2035 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.