Skip to Content

Brine cooler EA-G-445BG9-A01 C

Brine cooler EA-G-445BG9-A01 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-445BG9-A01 C

Cooling capacity i
26.13 kW
Air flow
18,860 m³/h
Fin spacing
9.0 mm
Air throw
19 m
Fans
4 × ⌀450 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Model nomenclature

How to read the code of this model.

  • B
    Number of fans: 4 — Digit 1-9.
  • C
    Fan diameter: 45 — Ø450 mm
  • E
    Coil tube rows (2nd dimensional letter): G — 8 tube rows
  • F
    Fin spacing: 9 — 9.0 mm
  • G
    Generation code: A — generation A
  • H
    Fan data (fan motor code): 01 — fan motor code; supply/poles vary with diameter

Data

Coil
Air flow 18,860 m³/h
Air throw 19 m
External surface 114.0 m²
Inner volume 58.2 dm³
Fin spacing 9.0 mm
Fin materialAluminium
Net weight 208 kg
Fans
Quantity 4
Diameter 450 mm
Speed 1,310 rpm
Power 1,960 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 58.0 dB(A)
Sound power 81.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-445BG9-A01 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · Single phase
26.130 kW Sensible capacity 19.050 kW Fluid flow 8.20 m³/h Pressure drop 29.0 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 12.09 10.64 10.52 ≈ 10.45
8 not rated not rated not rated not rated 19.31 18.33 ≈ 17.92 ≈ 29.94
10 not rated not rated not rated not rated 26.63 26.13 ≈ 39.90 44.41
12 not rated not rated not rated not rated not rated 47.52 52.46 57.67

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 26.130 8.20 29.0

Dimensions

Dimension drawing of EA-G-445BG9-A01 C
Dimension drawing
Dimensions as drawn
A 3167 mm
B 690 mm
C 675 mm
F 495 mm
E1 718 mm
E2 700 mm
E 2835 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3167 mm
Width 690 mm
Height 675 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.