EA-G-263GD4-A19 C
41.79 kW
Defrost: None
Product code: EA-G-263GC4-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 32,780 m³/h |
|---|---|
| Air throw | 42 m |
| External surface | 216.9 m² |
| Inner volume | 45.6 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 222 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263GC4-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.21 | ≈ 8.80 | ≈ 8.86 | ≈ 13.67 |
| 8 | not rated | not rated | not rated | not rated | ≈ 15.53 | ≈ 24.44 | ≈ 29.51 | ≈ 32.50 |
| 10 | not rated | not rated | not rated | not rated | ≈ 38.47 | 41.85 | 45.02 | 49.88 |
| 12 | not rated | not rated | not rated | not rated | not rated | 56.22 | 60.48 | 66.27 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.79 | 8.29 | ≈ 8.34 | ≈ 8.36 |
| 8 | not rated | not rated | not rated | not rated | ≈ 14.71 | ≈ 13.50 | ≈ 25.81 | ≈ 28.77 |
| 10 | not rated | not rated | not rated | not rated | ≈ 32.28 | 36.53 | 39.77 | 44.26 |
| 12 | not rated | not rated | not rated | not rated | not rated | 49.37 | 53.48 | 58.75 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 41.845 | 13.14 | 70.3 |
| Low speed (Y) | 36.531 | 11.47 | 55.3 |
| A | 3015 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| G | 935 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3015 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.