EA-G-550AE7-A09 C
48.27 kW
Defrost: None
Product code: EA-G-263GE7-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 32,005 m³/h |
|---|---|
| Air throw | 41 m |
| External surface | 219.7 m² |
| Inner volume | 67.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 256 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-263GE7-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 12.99 | ≈ 11.97 | ≈ 12.01 | ≈ 17.50 |
| 8 | not rated | not rated | not rated | not rated | ≈ 21.30 | ≈ 31.64 | ≈ 35.11 | ≈ 37.80 |
| 10 | not rated | not rated | not rated | not rated | ≈ 45.63 | 48.14 | 51.06 | 55.72 |
| 12 | not rated | not rated | not rated | not rated | not rated | 62.91 | 67.04 | 72.73 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 12.18 | ≈ 11.07 | ≈ 11.09 | ≈ 11.09 |
| 8 | not rated | not rated | not rated | not rated | ≈ 19.80 | ≈ 26.70 | ≈ 30.34 | ≈ 33.24 |
| 10 | not rated | not rated | not rated | not rated | 38.88 | 41.85 | 44.78 | 49.02 |
| 12 | not rated | not rated | not rated | not rated | not rated | 54.86 | 58.79 | 63.92 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 48.135 | 15.12 | 93.5 |
| Low speed (Y) | 41.848 | 13.14 | 73.0 |
| A | 3015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| G | 1035 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.