EA-G-450AE4-A10 C
48.28 kW
Defrost: None
Product code: EA-G-363FE10-A19 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 35,337 m³/h |
|---|---|
| Air throw | 31 m |
| External surface | 183.1 m² |
| Inner volume | 80.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 301 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,750 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-363FE10-A19 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 13.68 | ≈ 12.35 | ≈ 12.38 | ≈ 17.73 |
| 8 | not rated | not rated | not rated | not rated | ≈ 22.22 | ≈ 32.82 | ≈ 35.94 | ≈ 38.48 |
| 10 | not rated | not rated | not rated | not rated | ≈ 46.25 | 48.48 | 51.41 | 55.98 |
| 12 | not rated | not rated | not rated | not rated | not rated | 62.76 | 66.93 | 72.58 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 12.79 | ≈ 11.40 | ≈ 11.41 | ≈ 11.39 |
| 8 | not rated | not rated | not rated | not rated | ≈ 20.62 | ≈ 28.25 | ≈ 31.31 | ≈ 34.01 |
| 10 | not rated | not rated | not rated | not rated | 39.95 | 42.45 | 45.39 | 49.48 |
| 12 | not rated | not rated | not rated | not rated | not rated | 55.06 | 59.00 | 64.10 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 48.482 | 15.22 | 100.3 |
| Low speed (Y) | 42.446 | 13.33 | 79.3 |
| A | 3415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 3035 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.