EA-G-450AG4-A09 C
50.22 kW
Defrost: None
Product code: EA-G-363EE4-A06 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 23,196 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 300.7 m² |
| Inner volume | 62.5 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 283 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.9 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-363EE4-A06 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 12.95 | ≈ 11.94 | ≈ 11.99 | ≈ 17.78 |
| 8 | not rated | not rated | not rated | not rated | ≈ 21.31 | ≈ 32.94 | ≈ 36.17 | ≈ 39.73 |
| 10 | not rated | not rated | not rated | not rated | ≈ 47.15 | 50.13 | 53.48 | 58.37 |
| 12 | not rated | not rated | not rated | not rated | not rated | 65.46 | 70.11 | 76.05 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 11.88 | ≈ 10.76 | ≈ 10.79 | ≈ 10.74 |
| 8 | not rated | not rated | not rated | not rated | ≈ 19.32 | ≈ 25.65 | ≈ 29.33 | ≈ 33.01 |
| 10 | not rated | not rated | not rated | not rated | 37.34 | 41.02 | 44.28 | 48.45 |
| 12 | not rated | not rated | not rated | not rated | not rated | 53.75 | 57.93 | 62.97 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 50.133 | 15.75 | 94.2 |
| Low speed (Y) | 41.024 | 12.88 | 66.0 |
| A | 2815 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2815 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.