EA-G-263GD10-A19 C
30.35 kW
Defrost: None
Product code: EA-G-363FC10-A19 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 36,887 m³/h |
|---|---|
| Air throw | 32 m |
| External surface | 121.8 m² |
| Inner volume | 51.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 245 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,750 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 89.2 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-363FC10-A19 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.59 | 7.90 | ≈ 7.92 | ≈ 7.93 |
| 8 | not rated | not rated | not rated | not rated | 14.11 | ≈ 13.06 | ≈ 21.43 | ≈ 24.23 |
| 10 | not rated | not rated | not rated | not rated | ≈ 19.86 | 30.30 | 33.25 | 37.00 |
| 12 | not rated | not rated | not rated | not rated | not rated | 40.94 | 44.43 | 48.84 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.14 | 7.41 | ≈ 7.43 | ≈ 7.42 |
| 8 | not rated | not rated | not rated | not rated | 13.30 | ≈ 12.37 | ≈ 18.51 | ≈ 21.59 |
| 10 | not rated | not rated | not rated | not rated | ≈ 18.62 | 26.48 | 29.64 | 33.18 |
| 12 | not rated | not rated | not rated | not rated | not rated | 36.31 | 39.75 | 43.82 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 30.303 | 9.52 | 44.7 |
| Low speed (Y) | 26.478 | 8.32 | 35.2 |
| A | 3415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 3035 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3415 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.