EA-G-563EE4-A01 C
68.22 kW
Defrost: None
Product code: EA-G-363FG7-A19 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 32,839 m³/h |
|---|---|
| Air throw | 29 m |
| External surface | 338.0 m² |
| Inner volume | 104.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 358 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,750 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-363FG7-A19 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 18.88 | ≈ 17.15 | ≈ 17.19 | ≈ 25.97 |
| 8 | not rated | not rated | not rated | not rated | ≈ 44.15 | ≈ 46.74 | ≈ 50.06 | ≈ 54.17 |
| 10 | not rated | not rated | not rated | not rated | 65.32 | 68.23 | 72.15 | 78.24 |
| 12 | not rated | not rated | not rated | not rated | not rated | 87.95 | 93.59 | 101.19 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 17.54 | ≈ 15.68 | ≈ 15.70 | ≈ 21.30 |
| 8 | not rated | not rated | not rated | not rated | ≈ 28.21 | ≈ 39.61 | ≈ 42.90 | ≈ 46.98 |
| 10 | not rated | not rated | not rated | not rated | 55.36 | 58.64 | 62.40 | 67.67 |
| 12 | not rated | not rated | not rated | not rated | not rated | 75.67 | 80.81 | 87.32 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 68.229 | 21.42 | 112.7 |
| Low speed (Y) | 58.638 | 18.42 | 86.3 |
| A | 3415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 3035 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3415 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.