EA-G-663EC4-A11 C
97.25 kW
Defrost: None
Product code: EA-G-363GG4-A19 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 34,022 m³/h |
|---|---|
| Air throw | 30 m |
| External surface | 650.8 m² |
| Inner volume | 129.9 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 476 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,750 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-363GG4-A19 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 23.86 | ≈ 21.78 | ≈ 34.36 | 39.34 |
| 8 | not rated | not rated | not rated | not rated | ≈ 64.70 | ≈ 67.80 | ≈ 71.75 | 78.62 |
| 10 | not rated | not rated | not rated | not rated | 93.07 | 97.35 | 103.59 | 112.42 |
| 12 | not rated | not rated | not rated | not rated | not rated | 124.59 | 133.35 | 144.60 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 22.20 | ≈ 19.91 | ≈ 19.94 | ≈ 32.73 |
| 8 | not rated | not rated | not rated | not rated | ≈ 35.97 | ≈ 56.66 | ≈ 60.33 | ≈ 67.17 |
| 10 | not rated | not rated | not rated | not rated | ≈ 77.54 | 82.17 | 87.96 | 95.65 |
| 12 | not rated | not rated | not rated | not rated | not rated | 105.08 | 113.00 | 122.66 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 97.350 | 30.52 | 131.1 |
| Low speed (Y) | 82.166 | 25.77 | 97.1 |
| A | 4315 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4315 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.