Cooling capacity i
45.38 kW
Air flow
28,367 m³/h
Fin spacing
9.0 mm
Air throw
22 m
Fans
4 × ⌀500 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 28,367 m³/h
Air throw 22 m
External surface 115.4 m²
Inner volume 59.3 dm³
Fin spacing 9.0 mm
Fin materialAluminium
Net weight 218 kg
Fans
Quantity 4
Diameter 500 mm
Speed 1,360 rpm
Power 2,760 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 63.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-450BE9-A10 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
45.377 kW Sensible capacity 32.954 kW Fluid flow 14.25 m³/h Pressure drop 125.4 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
38.811 kW Sensible capacity 28.126 kW Fluid flow 12.19 m³/h Pressure drop 95.2 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 13.04 ≈ 11.47 ≈ 11.48 ≈ 17.01
8 not rated not rated not rated not rated ≈ 21.03 ≈ 30.64 ≈ 33.23 ≈ 37.09
10 not rated not rated not rated not rated ≈ 42.42 45.38 48.88 53.42
12 not rated not rated not rated not rated not rated 58.51 63.17 68.81

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 12.06 10.59 ≈ 10.46 ≈ 10.40
8 not rated not rated not rated not rated 19.28 ≈ 18.30 ≈ 28.38 ≈ 32.07
10 not rated not rated not rated not rated ≈ 26.60 38.81 42.17 46.21
12 not rated not rated not rated not rated not rated 50.26 54.54 59.48

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 45.377 14.25 125.4
Low speed (Y) 38.811 12.19 95.2

Dimensions

Dimension drawing of EA-G-450BE9-A10 C
Dimension drawing
Dimensions as drawn
A 3787 mm
B 640 mm
C 775 mm
F 560 mm
E1 868 mm
E2 850 mm
E 3435 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3787 mm
Width 640 mm
Height 775 mm

Downloads